Datasheet
Range of product | Modicon Quantum automation platform |
---|---|
Product or component type | Analogue safety input module |
Type of filter | Single pole low pass – 3 dB at 15 Hz |
Analogue input number | 8 |
---|---|
Addressing requirement | 13 input words |
Analogue input resolution | 16 bits |
linear measuring range | 0…25 mA |
Absolute maximum input | 35 mA |
Input impedance | 287 Ohm |
Absolute accuracy error | +/- 0.3 % +/- 0.35 % of full scale maximum |
Linearity error | +/- 2 µA max at 0…60 °C |
Common mode rejection | – 65 dB 60 Hz – 70 dB 50 Hz |
Isolation between channels and bus | 1500 V AC for 60 s |
Isolation between channels | 500 V AC for 60 s |
Update time | 15 ms |
Fault type | Overtacking scale |
Marking | CE |
Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 8 LEDs (green) for input status 8 LEDs (red) for system failure, diagnostic of internal channel fault |
Bus current requirement | 400 mA |
Power dissipation in W | 3.5 W |
Product certifications | UL C-Tick CSA HazLoc TÜV Rheinland (SIL2) CSA |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 4.7 cm |
Package 1 Width | 16.2 cm |
Package 1 Length | 31.5 cm |
Package 1 Weight | 500.0 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 3.9 kg |
Warranty | 18 months |
---|