Datasheet
Device short name | UI-8/AO-4 |
---|---|
Product or component type | I/O module |
Net weight | 152 g |
Flame retardance | UL94V0-5VB |
Height | 114 mm |
Product certifications | ICES-003 FCC part 15 class B CE RCM UL |
Width | 90 mm |
Depth | 64 mm |
Ambient air temperature for operation | 0…50 °C |
IP degree of protection | IP20 |
Ambient air temperature for storage | -20…70 °C |
Power consumption in W | 3.2 W |
Input/output type | universal input |
Relative humidity | 0…95 % non-condensing |
Number of outputs | 4 analog output |
[Us] rated supply voltage | 24 V DC |
Product name | I/O Modules |
Product brand | Schneider Electric |
Range | EcoStruxure Building Operation |
Control type | Without |
---|---|
Product compatibility | Johnson Control Xenta Balco Continuum Honeywell I/NET Satchwell |
Electrical connection | Plug-in sub-base |
Switching frequency | 25 Hz |
Discrete input number | 8 |
Mounting support | DIN rail Wall |
Analogue input type | Configurable voltage, current or probe 0…20 mA Configurable voltage, current or probe 0…10 V input voltage Configurable voltage, current or probe 20 kOhm connection of probes Configurable voltage, current or probe 10 kOhm connection of probes Configurable voltage, current or probe 2.2 kOhm connection of probes Configurable voltage, current or probe 1.8 kOhm connection of probes Configurable voltage, current or probe 1 kOhm connection of probes Configurable voltage, current or probe 10 kOhm with shunt |
Local signalling | LED (green/red) for high signal level LED (green/red) for low signal level |
Range compatibility | EcoStruxure Building Operation TB-IO-W1 terminal base |
Standards | UL 864 UL 916 FCC CFR47 part 15 |
Material | ABS + PC |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 5.6 cm |
Package 1 Width | 11.7 cm |
Package 1 Length | 9.1 cm |
Package 1 Weight | 170.0 g |