Datasheet
Range of product | Modicon Quantum automation platform |
---|---|
Product or component type | Mixed discrete I/O module |
Discrete I/O number | 8 |
Discrete input number | 4 1 group of 8 |
---|---|
Discrete input logic | Sink |
Addressing requirement | 1 input word 1 output word |
Network frequency limits | 47…63 Hz |
Discrete input voltage | 125 V DC |
Input voltage limits | 156.2 V including ripple |
Voltage state 0 guaranteed | 0…36 V |
Voltage state 1 guaranteed | 88…156.2 V |
Current state 0 guaranteed | <= 1.2 mA |
Current state 1 guaranteed | >= 2 mA |
Response time | 0.5 or 1.5 ms depending on the filter at at state 0 to state 1 0.5 or 1.5 ms depending on the filter at at state 1 to state 0 |
Discrete output number | 4 1 group of 4 |
Discrete output type | Solid state, isolated |
Discrete output logic | Source or sink |
Discrete output voltage | 24…125 V |
Output voltage limits | 19.2…156.2 V DC typical |
Maximum load current | <= 16 A per module <= 4 A per point |
Maximum voltage drop | <0.75 V 4 A |
Absolute maximum output | 30 A during 500 ms per point |
Maximum load capacitance | 0.1 µF 150 V DC 0.6 µF 24 V DC |
Maximum leakage current | 1.2 mA 150 V DC |
Protection type | Internal output protection by 5 A fuse per group On output by transient voltage suppression On input by resistor limited |
Associated fuse rating | 5 A |
Isolation between group of I/O channels | 1780 Vrms for 1 minute |
Isolation between group and bus | 2500 Vrms for 1 minute |
Isolation between channels | 1780 Vrms for 1 minute |
Fault indication | Overcurrent on output |
Power dissipation | 0.4 W + (1 x input point on) + (0.75 total output load current) |
Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for no voltage in output and input (F) 2 LEDs (red) for fault detected on the output point 4 LEDs (green) for output is turned on 4 LEDs (red) for fault detected on the input point |
Marking | CE |
Bus current requirement | 350 mA |
Net weight | 0.3 kg |
Resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 |
---|---|
Resistance to electromagnetic fields | 10 V/m 80…1000 MHz conforming to IEC 801-3 |
Ambient air temperature for operation | 0…60 °C |
Ambient air temperature for storage | -40…85 °C |
Relative humidity | 95 % without condensation |
Operating altitude | <= 5000 m |
Standards | UL 508 CSA C22.2 No 142 FM Class 1 Division 2 |
Product certifications | cUL |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 16.3 cm |
Package 1 Width | 4.5 cm |
Package 1 Length | 31.2 cm |
Package 1 Weight | 655.0 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 5.1 kg |
Warranty | 18 months |
---|