Range of product | Easergy T300 |
---|---|
Device short name | PS50 |
Product or component type | Power supply |
---|---|
Product compatibility | BAT38AH BAT24AH |
[Us] rated supply voltage | 110…220 V DC 90…264 V AC 50/60 Hz |
Output voltage | 12 V DC 24 V DC |
communication port protocol | Modbus |
Communication port support | RS485/RS232 |
Input voltage limits | 440 V AC/DC (L-N) |
Number of outputs | 1 digital (relay) battery fault (BAT): 1 digital (relay) main presence: |
Rated short-duration power frequency withstand voltage | 10 kV at 50 Hz during 1 min |
Surge withstand | 20 kV during 1.2/50 µs |
Protection type | Integrated thermal protection Against short-circuits |
Battery capacity | 24 Ah at 12 V, lead-acid battery 38 Ah at 12 V, lead-acid battery |
typical battery back-up autonomy | 16 h |
typical battery recharge time | 24 h |
Mounting support | DIN rail |
---|---|
Operating position | Vertical |
Overvoltage category | IV |
Electromagnetic compatibility | Electrical fast transient/burst immunity test – test level: level 4 criteria A conforming to IEC 61000-4-4 Conducted RF disturbances – test level: level 3 criteria A conforming to IEC 61000-4-6 Conducted disturbance emission – test level: level 4 criteria A conforming to IEC 61000-4-16 100 kHz damped oscillating wave – test level: level 3 criteria A conforming to IEC 61000-4-12 Radiated radio-frequency electromagnetic field immunity test – test level: level 4 criteria A conforming to IEC 61000-4-3 Immunity to voltage dips criteria A conforming to IEC 61000-4-29 Electrostatic discharge – test level: level 4 criteria B conforming to IEC 61000-4-2 Surge immunity test – test level: level 3 criteria A conforming to IEC 61000-4-5 Magnetic field at power frequency – test level: level 5 criteria B conforming to IEC 61000-4-8 Conducted and radiated emissions class A conforming to EN 55022 |
Standards | IEC 60255-27 |
Product certifications | CE |
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -40…70 °C |
Ambient air temperature for storage | -40…70 °C |
Relative humidity | 5…95 % conforming to IEC 60068-2-30 |
Operating altitude | 2000 m |
Mechanical robustness | Vibrations 10…2000 Hz 1 gn 10 cycles conforming to IEC 60068-2-6 Bumps 10 gn 16 ms 1000 bumps non energized conforming to IEC 60068-2-29 Shocks 10 gn 11 ms 3 pulses in operation conforming to IEC 60068-2-27 |
Height | 190 mm |
Width | 270 mm |
Depth | 71 mm |
Net weight | 2.75 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 13.3 cm |
Package 1 Width | 27 cm |
Package 1 Length | 36.3 cm |
Package 1 Weight | 3.11 kg |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 2 |
Package 2 Height | 30 cm |
Package 2 Width | 30 cm |
Package 2 Length | 40 cm |
Package 2 Weight | 6.699 kg |
Unit Type of Package 3 | P12 |
Number of Units in Package 3 | 16 |
Package 3 Height | 45 cm |
Package 3 Width | 80 cm |
Package 3 Length | 120 cm |
Package 3 Weight | 67 kg |