Datasheet
Range of product | Compact NS100…630 |
---|---|
Product or component type | Circuit breaker |
Device short name | Compact NS400N |
Circuit breaker name | Compact NS400N |
Device application | Distribution |
Poles description | 3P |
Protected poles description | 3t |
Network type | AC |
Network frequency | 50/60 Hz |
[In] rated current | 370 A at 65 °C 400 A at 40 °C |
[Ui] rated insulation voltage | 1250 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 1150 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code | N |
Breaking capacity | 10 kA Icu at 1000 V conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 10 kA at 1000 V conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |
Trip unit name | STR23SP |
Trip unit technology | Electronic |
Trip unit rating | 400 A |
Protection type | Instantaneous short-circuit protection Short time short-circuit protection Overload protection (long time) |
Pollution degree | 3 conforming to IEC 60947 |
Control type | Toggle |
---|---|
Mounting mode | Fixed |
Mounting support | Backplate |
upside connection | Front |
Downside connection | Front |
Circuit breaker CT rating | 250 A |
Mechanical durability | 15000 cycles |
Electrical durability | 2000 cycles 1000 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 1000 V AC 50/60 Hz In/2 conforming to IEC 60947-2 |
Connection pitch | 45 mm |
Local signalling | Positive contact indication |
Long time pick-up adjustment type Ir | Adjustable 48 settings |
long time pick-up adjustment range | 0.4…1 x In |
long time delay adjustment type | Fixed |
[tr] long-time delay adjustment range | 90…180 s 1.5 x Ir |
Short-time pick-up adjustment type Isd | Adjustable 8 settings |
[Isd] short-time pick-up adjustment range | 2…9 x Ir |
Short-time delay adjustment type | Fixed |
[tsd] short-time delay adjustment range | 0.04…0.06 s |
Instantaneous pick-up adjustment type Ii | Fixed |
Instantaneous pick-up adjustment range | >= 9 x In |
Display type | LED |
current sensor rating range | 150 A 250 A 400 A |
Height | 140 mm |
Width | 480 mm |
Depth | 110 mm |
Standards | IEC 60947-2 |
---|---|
Product certifications | ASEFA KEMA LCIE ASTA |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Warranty | 18 months |
---|