Schneider LC2F265

0.00

The price is not final. Please check with the manager!

Schneider Electric TeSys F reversing contactor – 3P(3 NO) AC-3 <= 440 V 265 A - without coil

Ask a Question

Datasheet

Main
RangeTeSys
Product nameTeSys F
Product or component typeReversing contactor
Device short nameLC2F
Contactor applicationMotor control
Resistive load
Utilisation categoryAC-3
AC-1
Device presentationPreassembled with reversing power busbar
Poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz
<= 460 V DC
[Ie] rated operational current350 A (at <40 °C) at <= 440 V AC AC-1
265 A (at <55 °C) at <= 440 V AC AC-3
Motor power kW132 kW at 380…400 V AC 50/60 Hz
140 kW at 415 V AC 50/60 Hz
140 kW at 440 V AC 50/60 Hz
147 kW at 1000 V AC 50/60 Hz
160 kW at 500 V AC 50/60 Hz
75 kW at 220…240 V AC 50/60 Hz
160 kW at 660…690 V AC 50/60 Hz
Auxiliary contact composition1 NO
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current350 A (at 40 °C)
Irms rated making capacity2650 A AC conforming to IEC 60947-4-1
Rated breaking capacity2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current2200 A 40 °C – 10 s
1230 A 40 °C – 30 s
950 A 40 °C – 1 min
620 A 40 °C – 3 min
480 A 40 °C – 10 min
Associated fuse rating315 A aM at <= 440 V
400 A gG at <= 440 V
Average impedance0.3 mOhm – Ith 350 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
Power dissipation per pole21 W AC-3
Interlocking typeMechanical
Mounting supportPlate
StandardsJIS C8201-4-1
IEC 60947-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-1
Product certificationsRMRoS
UL
LROS (Lloyds register of shipping)
DNV
CCC
RINA
CSA
ABS
CB
UKCA
Connections – terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: bar 2 cable(s) – busbar cross section: 32 x 4 mm
Tightening torqueControl circuit: 1.2 N.m
Power circuit: 35 N.m
Environment
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
Protective treatmentTH
Ambient air temperature for operation-5…55 °C
Ambient air temperature for storage-60…80 °C
Permissible ambient air temperature around the device-40…70 °C
Operating altitude3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open: 2 Gn, 5…300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Vibrations contactor closed: 5 Gn, 5…300 Hz
Shocks contactor open: 6 Gn for 11 ms
Height203 mm
Width425 mm
Depth213 mm
Net weight16.48 kg
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height25.0 cm
Package 1 Width30.0 cm
Package 1 Length62.0 cm
Package 1 Weight17.608 kg
Unit Type of Package 2P06
Number of Units in Package 24
Package 2 Height77.0 cm
Package 2 Width80.0 cm
Package 2 Length60.0 cm
Package 2 Weight78.932 kg
Contractual warranty
Warranty18 months

Reviews

Reviews about the product Schneider LC2F265