Datasheet
Device short name | VD 23 |
---|---|
Range of product | Easergy Flair |
Product or component type | Voltage detection relay |
Range compatibility | RM6 SM6-24 SM6-36 Flusarc Premset FBX |
Rated voltage (Ur) | 3…36 kV |
function available | Voltmeter |
---|---|
Local signalling | 1 LED for voltage presence phase to phase or phase to neutral 1 LED for voltage absence phase to phase or phase to neutral |
Supply | 24…48 V DC external supply |
Threshold setting | 40…90 % of Un 10 % increments voltage presence 10…30 % of Un 10 % increments voltage absence 30…60 % of Un 10 % increments residual voltage |
communication port protocol | Without |
Time delay setting | 0…1 s in steps of 0.1 s activation voltage relay 1…21 s in steps of 2 s activation voltage relay 1…15 min activation voltage relay 0…1 s in steps of 0.1 s release voltage relay 1…3 s in steps of 0.5 s release voltage relay |
Height | 48 mm |
Width | 96 mm |
Depth | 100 mm |
Net weight | 0.244 kg |
Electromagnetic compatibility | Electrostatic discharge – test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge – test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test – test level: 10 V/m, 80 MHz…1 GHz level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test – test level: 4 kV CM, 5kHz level 4 conforming to IEC 61000-4-4 Immunity to impulse waves – test level: 42 Ohm level 3 (on input-output) conforming to IEC 61000-4-5 Immunity to impulse waves – test level: 2 Ohm level 3 (on power supply) conforming to IEC 61000-4-5 Conducted RF disturbances – test level: 0.15…80 MHz, 10 V/m, 80 % MA (1 kHz) level 3 conforming to IEC 61000-4-6 Immunity to magnetic fields – test level: 30 A/m (permanent)-300 A/m (1 s) level 4 conforming to IEC 61000-4-8 Damped oscillating waves – test level: +/- 2.5 kV CM, +/- 1 kV DM, 1 MHz level 4 conforming to IEC 61000-4-12 |
---|---|
Mechanical robustness | Vibrations 9…200 Hz 1 gn 1 cycle conforming to IEC 60068-2-26 Seismic tests 2 gn horizontal position conforming to IEC 60068-2-29 Seismic tests 1 gn vertical position conforming to IEC 60068-2-29 Shocks 10 gn 11 ms 3 pulses in operation conforming to IEC 60068-2-27 |
IP degree of protection | Front panel: IP41 Other parts: IP30 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -40…70 °C |
Relative humidity | 95 % conforming to IEC 60068-2-30 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 7.2 cm |
Package 1 Width | 11.2 cm |
Package 1 Length | 13.9 cm |
Package 1 Weight | 242.0 g |
Unit Type of Package 2 | S04 |
Number of Units in Package 2 | 48 |
Package 2 Height | 30.0 cm |
Package 2 Width | 40.0 cm |
Package 2 Length | 60.0 cm |
Package 2 Weight | 13.3 kg |