Datasheet
| Range of product | Modicon Quantum automation platform |
|---|---|
| Product or component type | Analogue input module |
| Type of filter | Notch filter – 3 dB at 50/60 Hz Single pole low pass – 3 dB at 20 Hz |
| Analogue input number | 8 |
|---|---|
| Addressing requirement | 10 input words |
| Analogue input type | Thermocouple: – 210…760 °C for thermocouple J Thermocouple: – 270…1000 °C for thermocouple E Thermocouple: – 270…1370 °C for thermocouple K Thermocouple: – 270…400 °C for thermocouple T Thermocouple: – 50…1665 °C for thermocouple R Thermocouple: – 50…1665 °C for thermocouple S |
| Analogue input resolution | 16 bits |
| Absolute accuracy error | +/- 2 °C plus + 0.1 % of reading thermocouple E +/- 2 °C plus + 0.1 % of reading thermocouple J +/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S |
| Linearity error | 1 °C, 0.1 °C, 1 F, 0.1 F – 210…760 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…400 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 50…1665 °C |
| Accuracy drift according to temperature | 0.15 µV/°C + 0.0015 % of reading/°C max low level voltage |
| Common mode rejection | > – 120 dB 50/60 Hz |
| Isolation between channels and bus | 1780 V AC for 60 s 2500 V DC for 60 s |
| Isolation between channels | 300 V DC 220 V AC |
| Update time | 1000 ms |
| Fault type | Broken wire Overtacking scale |
| Marking | CE |
| Cold junction compensation | Internal 0…60 °C |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault |
| Bus current requirement | 280 mA |
| Power dissipation in W | 1.5 W |
| Module format | Standard |
| Net weight | 0.3 kg |
| Standards | CSA C22.2 No 142 UL 508 |
|---|---|
| Product certifications | cUL FM Class 1 Division 2 |
| Resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 |
| Resistance to electromagnetic fields | 10 V/m 80…1000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 95 % without condensation |
| Operating altitude | <= 5000 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 16.500 cm |
| Package 1 Length | 31.500 cm |
| Package 1 Weight | 425.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.456 kg |
| Warranty | 18 months |
|---|