Datasheet
| Range | PowerLogic |
|---|---|
| Product name | PowerLogic BCPM |
| Product or component type | Multi-circuit energy meter |
| Device short name | BCPMA |
| Model type | Advanced |
| Power monitoring | Basic instrumentation |
| Energy management | Sub billing and cost allocation |
| Device application | Sub billing |
| Power quality analysis | voltage sag and swell detection |
| Type of measurement | Voltage Current Frequency Active power Power factor Active energy |
| [Us] rated supply voltage | 90…277 V AC 50/60 Hz +/- 1 % |
| Network frequency | 50 Hz 60 Hz |
| current transformer input | Solid core CT 100 A84 x |
|---|---|
| Update time | 1.8 s |
| Measurement voltage | 90…277 V phase to neutral 150…480 V phase to phase |
| Measurement accuracy | Branch current 2 % 0.25…2 A Branch current 1 % 2…100 A Mains current 3 % 1…100 % Mains current 3 % 2…100 % Voltage 1 % 90…277 V |
| Sampling rate | 256 samples/cycle |
| Connection pitch | 19 mm |
| Provided equipment | 84 x current transformer 4 x cables |
| Communication port protocol | Modbus RTU |
| Communication port support | RS485 |
| Communication of data | Low-low current alarm Low current alarm Under voltage alarm High current alarm Over voltage alarm High-high current alarm |
| Mounting mode | Panel-mounted |
|---|---|
| Mounting support | Panel Enclosure |
| Relative humidity | 0…95 % at 0…60 °C |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 3000 m |
| Standards | ANSI C12.1 EN 61010 IEC 61036 UL 508 |
| Product certifications | UL |
| Width | 288 mm |
| Height | 146 mm |
| Net weight | 1.5 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 159 cm |
| Package 1 Width | 248 cm |
| Package 1 Length | 794 cm |
| Package 1 Weight | 4522.73 g |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 50 cm |
| Package 2 Width | 80 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 35.5 kg |
| Warranty | 18 months |
|---|