Datasheet
| Range of product | Easergy T300 |
|---|---|
| Device short name | SC150 |
| Product or component type | MV switch controller |
|---|---|
| protection or fault passage indication function | ANSI 50/51 : overcurrent ANSI 50N/51N : earth fault ANSI 67 : directional phase overcurrent ANSI 67N : directional earth fault ANSI 47 : negative sequence overvoltage ANSI 27 : undervoltage ANSI 59 : overvoltage ANSI 59N : neutral voltage displacement ANSI 37 : phase undercurrent |
| power measurement | Voltage Frequency Current |
| measurement accuracy | Current: class 0.5 Voltage: class 0.5 |
| Data recording | Counter Current value before fault Sequence of event recording Event logs Demand values |
| Memory capacity | 4 MB |
| Synchronisation time between inputs | 1 ms |
| Control type | Illuminated push-button status: |
| web services | Alarm Event log Assistance in commissioning and operating the installation Security/authority verification Reports and diagrams Operating/Status report |
| [Us] rated supply voltage | 12…48 V DC +/- 20 % |
| Power consumption in VA | 2 VA |
| communication port protocol | IEC 60870-5-104 |
| Communication port support | ETHERNET 2 RJ45 |
| Number of inputs | 8 digital conforming to IEC 61131-2 type 3 |
| Measurement current | 1 A 5 A |
| Analogue input type | Current 0.01…35 A (impedance 0.001 Ohm)4 x |
| Measurement voltage | : 0…30 V VPIS AC at 50/60 Hz (single or three phases) : 0…30 V VDS LRM AC at 50/60 Hz (single or three phases) : 0…30 V PPACS AC at 50/60 Hz (single or three phases) |
| Number of outputs | 2 digital (relay) switch: |
| Maximum switching voltage | 440 V AC |
| rated motor mechanism voltage | 12…127 V DC motor: 90…220 V AC motor: |
| Continuous output current | 8 A |
| Breaking capacity | 2000 VA |
| Irms rated making capacity | 15 A during 4 s |
| Fixing mode | Clip-in (DIN rail) |
|---|---|
| Type of installation | Indoor Outdoor in cabinet |
| Electromagnetic compatibility | Electrical fast transient/burst immunity test – test level: level 4 criteria A conforming to IEC 61000-4-4 Conducted RF disturbances – test level: level 3 criteria A conforming to IEC 61000-4-6 Conducted disturbance emission – test level: level 4 criteria A conforming to IEC 61000-4-16 100 kHz damped oscillating wave – test level: level 3 criteria A conforming to IEC 61000-4-12 Radiated radio-frequency electromagnetic field immunity test – test level: level 4 criteria A conforming to IEC 61000-4-3 Immunity to voltage dips criteria A conforming to IEC 61000-4-29 Electrostatic discharge – test level: level 4 criteria B conforming to IEC 61000-4-2 Surge immunity test – test level: level 3 criteria A conforming to IEC 61000-4-5 Magnetic field at power frequency – test level: level 5 criteria B conforming to IEC 61000-4-8 Conducted and radiated emissions class A conforming to EN 55022 |
| IP degree of protection | IP2X body: conforming to IEC 60529 IP4X front: conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Relative humidity | 5…95 % conforming to IEC 60068-2-30 |
| Mechanical robustness | Vibrations 10…2000 Hz 1 gn 10 cycles conforming to IEC 60068-2-6 Bumps 10 gn 16 ms 1000 bumps non energized conforming to IEC 60068-2-29 Shocks 10 gn 11 ms 3 pulses in operation conforming to IEC 60068-2-27 |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 2000 m |
| Product certifications | CE |
| Standards | IEC 60255-27 IEC 61557-12 IEC 62586-1 IEC 61000-4-30:class S IEC 61850 |
| Height | 140 mm |
| Width | 45 mm |
| Depth | 140 mm |
| Net weight | 0.515 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.0 cm |
| Package 1 Width | 19.0 cm |
| Package 1 Length | 20.0 cm |
| Package 1 Weight | 668.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 5.794 kg |