Datasheet
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 380…480 V (+/- 10 %) |
| Network frequency | 50/60 Hz |
| Range compatibility | Altivar 61 Altivar 71 |
| Product specific application | Component of the Active Front End |
| Assembly style | Built-in unit |
| Type of cooling | Natural convection |
| Product destination | 1 active infeed converter (AIC) VW3A7251 1 active infeed converter (AIC) VW3A7252 |
| Maximum number of switchings | 10 per hour |
| Line current | 255 A at 50 В°C |
| Thermal losses | 360 W |
| Electrical connection | Bar M10 – 95 mmВІ 24 N.m (PE) Terminal – 2.5 mmВІ 0.6…0.8 N.m (X1:1…X1:6) Bar M10 – 2 x 95 mmВІ 24 N.m (1L1, 1L2, 1L3) Bar M12 – 2 x 95 mmВІ 14…31 N.m (2L1, 2L2, 2L3) Bar M10 – 150 mmВІ 24 N.m (1L1, 1L2, 1L3) Bar M12 – 185 mmВІ 14…31 N.m (2L1, 2L2, 2L3) |
| Output type | Control electronics for AIC and inverter 24 V DC Fan for AIC and 4 inverters of the same power 380…480 V AC |
| Device Full Name | Schneider Electric VW3A7261 |