Datasheet
| Range | TeSys |
|---|---|
| Product name | TeSys F |
| Product or component type | Contactor |
| Device short name | LC1F |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz |
| [Ie] rated operational current | 2600 A (at <60 °C) at <= 440 V AC AC-1 |
| [Uc] control circuit voltage | 110…500 V AC 40…400 Hz with LX1/LX9 coil 110…440 V DC with LX4 coil |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 2600 A (at 60 °C) |
| Irms rated making capacity | 3900 A AC conforming to IEC 60947-4-1 |
| Rated breaking capacity | 3900 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 12000 A 40 °C – 10 s 9000 A 40 °C – 30 s 7000 A 40 °C – 1 min 6000 A 40 °C – 3 min 4000 A 40 °C – 10 min |
| Associated fuse rating | 2500 A gG at <= 440 V |
| Average impedance | 0.1 mOhm – Ith 2600 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 |
| Power dissipation per pole | 250 W AC-1 |
| Control circuit voltage limits | Operational: 0.85…1.1 Uc AC 40…400 Hz with LX1/LX9 coil Drop-out: 0.3…0.5 Uc AC 40…400 Hz with LX1/LX9 coil Operational: 0.85…1.1 Uc DC with LX4 coil Drop-out: 0.2…0.35 Uc DC with LX4 coil |
| Heat dissipation | 25 W |
| Operating time | 40…80 ms closing for with LX1/LX9 coil 100…200 ms opening for with LX1/LX9 coil 60…70 ms closing for with LX4 coil 40…50 ms opening for with LX4 coil |
| Mounting support | Plate |
| Standards | IEC 60947-1 IEC 60947-4-1 EN 60947-4-1 JIS C8201-4-1 EN 60947-1 |
| Product certifications | cETLus CCC CSA CB UKCA |
| Connections – terminals | Power circuit: bar 3 cable(s) – busbar cross section: 100 x 10 mm Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² |
| Tightening torque | Power circuit: 58 N.m Control circuit: 1.2 N.m |
| Mechanical durability | 0.5 Mcycles |
| Inrush power in VA | 2200…2700 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 2130…2880 VA (at 20 °C)with LX4 coil |
| Hold-in power consumption in VA | 37.4…50.6 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 13…25 VA (at 20 °C)with LX4 coil |
| Maximum operating rate | 600 cyc/h 55 °C |
| Compatibility code | LC1F |
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
|---|---|
| Protective treatment | TH |
| Ambient air temperature for operation | -5…40 °C |
| Ambient air temperature for storage | -60…80 °C |
| Permissible ambient air temperature around the device | -40…60 °C |
| Operating altitude | 3000 m without derating |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5…300 Hz Vibrations contactor closed: 4 Gn, 5…300 Hz Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms) Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms) |
| Height | 382 mm |
| Width | 519 mm |
| Depth | 251 mm |
| Net weight | 36 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 45.72 cm |
| Package 1 Width | 50.8 cm |
| Package 1 Length | 60.96 cm |
| Package 1 Weight | 37.65 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 1 |
| Package 2 Height | 77 cm |
| Package 2 Width | 80 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 45.5 kg |
| Warranty | 18 months |
|---|