Datasheet
| Range | ComPact |
|---|---|
| Range of product | ComPact NSX400…630 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 6.3 E |
| Trip unit technology | Electronic |
| Range compatibility | ComPact NSX400 ComPact NSX630 |
| Device application | Generator Distribution |
| Number of poles | 4P |
| Protected poles description | 3t 4t 3t + N/2 3t + OSN |
| Neutral position | Left |
| Trip unit protection functions | LSIG |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection |
| Trip unit rated current | 400 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 160…400 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5…10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5…11 x In Compact NSX630 1.5…12 x In Compact NSX400 |
| Ground-fault protection pick-up adjustment type Ig | Adjustable |
| [Ig] ground-fault protection pick-up adjustment range | 0.2…1 x In |
| Ground-fault protection time delay adjustment type tg | Adjustable |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) No protection (3t) |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| type of measurement | Energy meter |
| Communication of data | Maximeters/minimeters Protection and alarm settings Demand current and power Maintenance indicators Power quality Instantaneous and demand values Time-stamped histories and event tables Energy metering |
| Electrical data recording | Maintenance indicators |
| Standards | UL 508 EN/IEC 60947-2 |
|---|---|
| Product certifications | EAC CCC Marine |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.0 cm |
| Package 1 Width | 17.5 cm |
| Package 1 Length | 21.5 cm |
| Package 1 Weight | 1.82 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 40.0 cm |
| Package 2 Length | 60.0 cm |
| Package 2 Weight | 18.88 kg |
| Warranty | 18 months |
|---|