Datasheet
| Range of product | AccuSine |
|---|---|
| Product name | AccuSine PCSn |
| Product or component type | Active harmonic filter |
| Network type | 3P + N 3P |
|---|---|
| Network configuration | 3 or 4 wires |
| Network rated voltage | 208…415 V AC |
| Network frequency | 50/60 Hz |
| maximum permissible voltage | 1.1 x Un |
| RMS output current rating | 30 A |
| Reactive power rating | 21.6 kvar 415 V AC 50/60 Hz |
| Operating modes | Phase harmonic correction Neutral harmonic correction Mains current balancing Power factor correction |
| Installation location | Indoor |
| Mounting mode | Wall-mounted |
| Protection type | Without protection |
| Heat dissipation | Rear plenum with forced ventilation for high heat flow |
| Electromagnetic compatibility | Electromagnetic emission, class A conforming to EN 61000-6-4 Electromagnetic immunity conforming to EN 61000-6-2 |
| Accessibility for operation | Front |
| Location of connection | Bottom |
| Enclosure degree of protection | IP20 |
|---|---|
| Environmental characteristic | Operating: 3C2 conforming to IEC 60721-3-3 Operating: 3S2 conforming to IEC 60721-3-3 Storage: 3C3 conforming to IEC 60721-3-3 Storage: 3S3 conforming to IEC 60721-3-3 |
| Operating altitude | <= 1000 m 1 % per 100 m 0…4800 m |
| Ambient air temperature for operation | 0…40 °C 0…50 °C maximum with current derating of 2 % per °C above 40 °C |
| Relative humidity | 0…95 % non-condensing |
| PCBA protection | Conformal coated |
| Standards | IEC 62477-1 IEC 61439-1 EN 61000-6-2 EN 61000-6-4 ISO 9001 IEEE 519-2014 |
| Product certifications | RCM EAC CE ABS IBC 2015 (Seismic) ICC-ES AC156 |
| Ambient air temperature for storage | -20…60 °C |
| Net weight | 61 kg |
| Height | 960 mm |
| Width | 440 mm |
| Colour | Light grey (RAL 7035) |
| Depth | 265 mm |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 26.4 cm |
| Package 1 Width | 46.5 cm |
| Package 1 Length | 96.0 cm |
| Package 1 Weight | 88.0 kg |