Datasheet
| Lead time | Usually Ships within 2 Weeks |
|---|
Run time for load
W Enter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.
Min-max: 1600-16000 W
|
|
|---|---|
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.
|
|
| Main Input Voltage | 400 V 3 phases |
| Other Input Voltage | 380 V 415 V |
| Main Output Voltage | 400 V 3 phases |
| Other Output Voltage | 380 V 415 V |
| rated power in W | 16000 W |
| Rated power in VA | 20000 VA |
| Output connector type | Hard wire 4-wire (3P + E) 1 Hard wire 5-wire (3P + N + E) 1 |
| Connections – terminals | 1 screw terminals |
| Battery type | VRLA |
| Provided equipment | Battery modules ship installed CD with software Network management card Power modules ship installed User manual Bolt down brackets Installation guide Start up included |
| Run Time | View Runtime Graph |
|---|---|
| Efficiency | View Efficiency Graph |
| Number of battery filled slots | 4 |
| Number of battery free slots | 0 |
| Battery recharge time | 5 h |
| Number of battery replacement quantity | 4 |
| Additional information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
| Battery voltage | +/- 192 V (split battery referenced to neutral) |
| Discharge battery voltage | +/- 154 V |
| Battery charger power | 1958 W rated |
| Battery power in VAH | 9810 VAh runtime |
| Battery life | 3…5 year(s) |
| Battery option | SUVTXR2B6S 1 14715 VAh SUVTXR6B6S 1 24526 VAh SUVTXR6B6S 2 39329 VAh SUVTXR6B6S 3 54321 VAh SUVTXR6B6S 4 69523 VAh |
| Battery graph comments | Estimated runtimes based on battery vendor data, at typical environmental conditions, with no electrical input and balanced PF = 0.8 output. |
| Extended runtime | 1 |
| Number of power module free slots | 0 |
|---|---|
| Number of power module filled slots | 0 |
| Redundant | Yes |
| Colour | Black |
|---|---|
| Height | 149 cm |
| Width | 52.3 cm |
| Depth | 84.2 cm |
| Net weight | 599.09 kg |
| Mounting location | Front |
| Mounting preference | No preference |
| Mounting mode | Not rack-mountable |
| Two post mountable | 0 |
| USB compatible | No |
| Network frequency | 40…70 Hz auto-sensing |
|---|---|
| Number of input connectors | 1 hard wire 5-wire (3P + N + E) |
| Input voltage limits | 304…477 V |
| Maximum input current | 27 A |
| Switching current capacity | 50 A |
| Input Power Factor at Full Load | 0.98 |
| Maximum configurable power in W | 16000 W |
|---|---|
| Harmonic distortion | Less than 5 % at full load |
| Output frequency | 47…53 Hz for 50 Hz nominal sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
| Crest factor | 3 : 1 |
| UPS type | Double conversion online |
| Wave type | Sine wave |
| bypass type | Built-in maintenance bypass Built-in static bypass |
| Maximum output current | 32 A |
| Maximum configurable power in VA | 20000 VA |
| Product certifications | C-Tick CE RCM |
|---|
| Ambient air temperature for operation | 0…40 °C |
|---|---|
| Relative humidity | 0…95 % |
| Operating altitude | 0…3333 ft |
| Ambient air temperature for storage | -50…40 °C |
| Storage Relative Humidity | 0…95 % |
| Storage altitude | 0.00…15240.00 m |
| Acoustic level | 51.3 dBA |
| heat dissipation | 3112 Btu/h |
| IP degree of protection | IP20 |
| Free slots | 0 |
|---|---|
| Preinstalled device | Network management card 2 with environmental monitoring |
| Emergency power off | Yes |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 164.3 cm |
| Package 1 Width | 106.2 cm |
| Package 1 Length | 65 cm |
| Package 1 Weight | 630 kg |
| Number of Units in Package 3 | 1 |
| Warranty | 1 year repair or replace, Start-Up Service |
|---|