Datasheet
| Presentation | High performance, redundant power protection with scalable power and runtime for space-constrained server rooms, and voice and data networks. |
|---|---|
| Lead time | Usually in Stock |
| Main Input Voltage | 230 V 400 V 3 phases |
|---|---|
| Other Input Voltage | 220 V 240 V 380 V 415 V |
| Main Output Voltage | 230 V |
| Other Output Voltage | 220 V 240 V |
| rated power in W | 11200 W |
| Rated power in VA | 16000 VA |
| output connection type | 8 IEC 60320 C13 10 IEC 60320 C19 |
| Output connector type | Hard wire 3-wire (H N + E) 1 |
| Number of rack unit | 19U |
| Battery type | Lead-acid battery |
| Provided equipment | CD with software Documentation CD Installation guide User manual Web/SNMP management card |
| Number of battery filled slots | 0 |
|---|---|
| Number of battery free slots | 4 |
| Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
| Battery power in VAH | 0 VAh runtime |
| Battery life | 3…5 year(s) |
| Extended runtime | 1 |
| Number of power module free slots | 5 |
|---|---|
| Number of power module filled slots | 0 |
| Redundant | Yes |
| Colour | Black Silver |
|---|---|
| Height | 83.8 cm |
| Width | 47.2 cm |
| Depth | 68.8 cm |
| Net weight | 95.45 kg |
| Mounting location | Front |
| Mounting preference | Lower |
| Mounting mode | Rack-mounted |
| Two post mountable | 0 |
| USB compatible | No |
| Network frequency | 45…65 Hz auto-sensing |
|---|---|
| Number of input connectors | 1 hard wire 3-wire (1P + N + E) 1 hard wire 5-wire (3P + N + E) |
| Input voltage limits | 155…276 V 290…480 V 3:1 |
| Input Power Factor at Full Load | 0.98 |
| Maximum configurable power in W | 11200 W |
|---|---|
| Harmonic distortion | Less than 5 % at full load |
| Output frequency | 47…63 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
| Crest factor | Up to 5 : 1 |
| UPS type | Double conversion online |
| Wave type | Sine wave |
| bypass type | Internal bypass (automatic and manual) |
| Efficiency | 90 % (full load) |
| Maximum output current | 73 A |
| Maximum configurable power in VA | 16000 VA |
| Product certifications | C-Tick CE GOST VDE |
|---|---|
| Standards | EN 50091-1 EN 50091-2 EN 55022 class A EN 55024 EN 60950 IEC 60950 |
| Ambient air temperature for operation | 0…40 °C |
|---|---|
| Relative humidity | 5…95 % |
| Operating altitude | 0…10000 ft |
| Ambient air temperature for storage | -15…45 °C |
| Storage Relative Humidity | 5…95 % |
| Storage altitude | 0.00…4572.00 m |
| Acoustic level | 62 dBA |
| heat dissipation | 3707 Btu/h |
| Free slots | 1 |
|---|---|
| Preinstalled device | Network management card with environmental monitoring |
| control panel | Multifunction LCD status and control console |
| Alarm | Audible and visible alarms : prioritized by severity |
| Emergency power off | Yes |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 105.4 cm |
| Package 1 Width | 99.7 cm |
| Package 1 Length | 59.9 cm |
| Package 1 Weight | 120.45 kg |
| Warranty | 2 years repair or replace |
|---|