Datasheet
Product characteristics
| Laser protection class | 2 |
|---|---|
| Housing | rectangular |
Electrical data
| Operating voltage [V] | 18…30 DC; (“supply class 2” to cULus) |
|---|---|
| Current consumption [mA] | < 150 |
| Protection class | III |
| Reverse polarity protection | yes |
| Typ. lifetime [h] | 50000 |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
|---|
Outputs
| Total number of outputs | 2 |
|---|---|
| Electrical design | PNP |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (programmable) |
| Max. current load per output [mA] | 200 |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4…20; (scalable IEC 61131-2) |
| Max. load [Ω] | 250 |
| Analogue voltage output [V] | 0…10; (scalable IEC 61131-2) |
| Min. load resistance [Ω] | 5000 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Detection zone
| Max. light spot width [mm] | 15 |
|---|---|
| Max. light spot height [mm] | 15 |
| Light spot dimensions refer to | 10 m |
| Background suppression [m] | 10…100 |
Measuring/setting range
| Measuring range [m] | 0.2…10; (white paper 200 x 200 mm 90% remission) |
|---|---|
| Sampling rate [Hz] | 1…33 |
Interfaces
| Communication interface | IO-Link | ||||
|---|---|---|---|---|---|
| Transmission type | COM2 (38,4 kBaud) | ||||
| IO-Link revision | 1.1 | ||||
| SDCI standard | IEC 61131-9 | ||||
| Profiles | Smart Sensor: Device Identification; Device Diagnosis; Device Teach Channel; Binary Data Channel; Process Data Variable | ||||
| SIO mode | yes | ||||
| Required master port type | A | ||||
| Process data analogue | 2 | ||||
| Process data binary | 2 | ||||
| Min. process cycle time [ms] | 6 | ||||
| Supported DeviceIDs |
|
Operating conditions
| Ambient temperature [°C] | -10…60 |
|---|---|
| Protection | IP 67 |
Tests / approvals
| EMC |
|
||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Laser protection class | 2 | ||||||||||||||||||||
| Notes on laser protection |
|
||||||||||||||||||||
| UL approval |
|
Mechanical data
| Weight [g] | 248.1 |
|---|---|
| Housing | rectangular |
| Dimensions [mm] | 59 x 42 x 52 |
| Materials | housing: diecast zinc; front pane: glass; LED window: PC |
| Lens alignment | side lens |
Displays / operating elements
| Display |
|
|---|
Accessories
| Accessories (optional) |
|
|---|
Remarks
| Remarks |
|
|
|---|---|---|
| Pack quantity | 1 pcs. |
Electrical connection
| Connection | Connector: 1 x M12; coding: A |
|---|
Other data
| Parameter | Setting range | Factory setting |
| Uni | mm, m | mm |
| OU1 | Hno, Hnc, Fno, Fnc | Hno |
| SP1 | 200…9999 | 1000 |
| nSP1 | 200…9999 | 800 |
| FSP1 | 200…9999 | 1200 |
| OU2 | Hno, Hnc, Fno, Fnc, I, U | I |
| SP2 | 200…9999 | 2000 |
| nSP2 | 200…9999 | 1800 |
| FSP2 | 200…9999 | 2200 |
| ASP | 0…9999 | 0 |
| AEP | 0…9999 | 9999 |
| rATE [Hz] | 1…33 | 15 |
| dS1 | 0…0.1…5 | 0 |
| dr1 | 0…0.1…5 | 0 |
| dS2 | 0…0.1…5 | 0 |
| dr2 | 0…0.1…5 | 0 |
| dFo | 0…0.1…5 | 0 |
| dIS | d1…3; rd1…3; OFF | d3 |
repeatability/accuracy
| repeatability of the measured values | accuracy | |||
| white (90 % remission) | grey (18 % remission) | white (90 % remission) | grey (18 % remission) | |
| 200…1000 mm | ± 4.5 mm | ± 6.0 mm | ± 15.0 mm | ± 16.0 mm |
| 1000…2000 mm | ± 5.0 mm | ±8.0 mm | ± 15.0 mm | ± 18.0 mm |
| 2000…4000 mm | ± 16.0 mm | ±19.0 mm | ± 25.0 mm | ± 30.0 mm |
| 4000…6000 mm | ± 24.0 mm | ± 33.0 mm | ± 35.0 mm | ± 45.0 mm |
| 6000…10000 mm | ± 50.0 mm | – | ± 65.0 mm | – |
| Sampling rate | 15 Hz |
| Extraneous light on the object | < 40 klx |
repeatability/accuracy
| repeatability of the measured values | accuracy | |||
| white (90 % remission) | grey (18 % remission) | white (90 % remission) | grey (18 % remission) | |
| 200…2000 mm | ± 14.0 mm | ± 14.0 mm | ± 24.0 mm | ± 24.0 mm |
| 2000…4000 mm | ± 25.0 mm | ± 30.0 mm | ± 35.0 mm | ± 40 mm |
| 4000…6000 mm | ± 31.0 mm | ±45.0 mm | ± 41.0 mm | ± 55.0 mm |
| 6000…10000 mm | ± 60.0 mm | – | ± 70.0 mm | – |
| Sampling rate | 15 Hz |
| Extraneous light on the object | < 40…100 klx |
| Range on black object (6 % remission) | <= 4000 klx |
| The values apply at | |
| constant ambient conditions | 23 °C / 960 hPa |
| minimum power-on time in minutes | 10 |