€422.68
The price is not final. Please check with the manager!
Contact Sales
Returns
14 days return. New condition only.
Shipping
EU, USA, worldwide.
DHL, DPD, UPS.
Datasheet
Product characteristics
| Measuring range |
|
1…50 l/min |
0.06…3 m³/h |
16…793 gph |
0.26…13.2 gpm |
|
| Process connection |
threaded connection G 1 internal thread |
Application
| Special feature |
Gold-plated contacts |
| Media |
Liquids; oils (viscosity 150 mm²/s at 40 °C) |
| Medium temperature [°C] |
-10…100 |
| Pressure rating [bar] |
100 |
| Pressure rating [Mpa] |
10 |
| Note on pressure rating |
|
at medium temperature >70°C: 80 bar / 8 MPa |
|
Electrical data
| Operating voltage [V] |
18…30 DC; (to SELV/PELV) |
| Current consumption [mA] |
< 50 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 3 |
Outputs
| Total number of outputs |
2 |
| Output signal |
switching signal; analogue signal; frequency signal; IO-Link |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2 |
| Max. current load per output [mA] |
150; (200: …60 °C; Ambient temperature; 250: …40 °C; Ambient temperature) |
| Analogue current output [mA] |
4…20 |
| Max. load [Ω] |
500 |
| Short-circuit protection |
yes |
| Overload protection |
yes |
| Frequency of the output [Hz] |
0…10000 |
Measuring/setting range
| Measuring range |
|
1…50 l/min |
0.06…3 m³/h |
16…793 gph |
0.26…13.2 gpm |
|
| Display range |
|
0…60 l/min |
0…3.6 m³/h |
0…951 gph |
0…15.86 gpm |
|
| Resolution |
|
0.01 l/min |
0.001 m³/h |
1 gph |
0.01 gpm |
|
| Set point SP |
|
0.35…50 l/min |
0.02…3 m³/h |
5…793 gph |
0.08…13.2 gpm |
|
| Reset point rP |
|
0…49.65 l/min |
0…2.98 m³/h |
0…787 gph |
0…13.12 gpm |
|
| Frequency end point, FEP |
|
3.35…50 l/min |
0.2…3 m³/h |
53…793 gph |
0.88…13.2 gpm |
|
| In steps of |
|
0.05 l/min |
0.005 m³/h |
1 gph |
0.02 gpm |
|
| Frequency at the end point FRP [Hz] |
10…10000 |
| In steps of [Hz] |
10 |
| Measuring dynamics |
1:50 |
Temperature monitoring
| Measuring range |
|
| Display range |
|
-32…122 °C |
-25.6…251.6 °F |
|
| Resolution |
|
| Set point SP |
|
| Reset point rP |
|
| In steps of |
|
| Frequency start point, FSP |
|
| Frequency end point, FEP |
|
| Frequency at the end point FRP [Hz] |
10…10000 |
| In steps of [Hz] |
10 |
Accuracy / deviations
Flow monitoring
| Accuracy (in the measuring range) |
± 5 % MEW; (Q > 1 l/min; 20…70 °C Medium temperature) |
| Repeatability |
± 1 % MEW |
Temperature monitoring
| Temperature drift |
0,029 °C / K |
| Accuracy [K] |
3 K (25°C; Q > 1 l/min) |
Response times
Flow monitoring
| Response time [s] |
0.01 |
| Damping process value dAP [s] |
0…5 |
| In steps of [s] |
0.1 |
| Damping for the analogue output dAA [s] |
0…5 |
| In steps of [s] |
0.1 |
Temperature monitoring
| Dynamic response T05 / T09 [s] |
T09 = 120 (Q > 1 l/min) |
Software / programming
| Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; current/frequency output; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour; calibration factor |
Interfaces
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 CDV |
| Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode |
yes |
| Required master port type |
A |
| Process data analogue |
2 |
| Process data binary |
2 |
| Min. process cycle time [ms] |
3.2 |
| Supported DeviceIDs |
|
Type of operation |
DeviceID |
|
Default |
1045 |
|
Operating conditions
| Ambient temperature [°C] |
0…60 |
| Note on ambient temperature |
|
medium temperature < 80 °C |
|
medium temperature < 100 °C: 0...40 °C |
|
| Storage temperature [°C] |
-15…80 |
| Protection |
IP 65; IP 67 |
Tests / approvals
| EMC |
|
DIN EN 61000-6-2 |
|
|
DIN EN 61000-6-3 |
|
|
| Shock resistance |
|
DIN EN 60068-2-27 |
20 g (11 ms) |
|
| Vibration resistance |
|
DIN EN 60068-2-6 |
5 g (10…2000 Hz) |
|
| UL approval |
|
| Pressure Equipment Directive |
Sound engineering practice |
Mechanical data
| Weight [g] |
1571.5 |
| Materials |
stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated |
| Materials (wetted parts) |
stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; O-ring: FKM |
| Process connection |
threaded connection G 1 internal thread |
| Switching cycles mechanical |
10 million |
Displays / operating elements
| Display |
|
Display unit |
6 x LED, green |
|
switching status |
2 x LED, yellow |
|
measured values |
alphanumeric display, red/green alternating indication 4-digit |
|
programming |
alphanumeric display, 4-digit |
|
Remarks
| Remarks |
|
Recommendation: use a 200-micron filter. |
|
All data refer to oil with the following nominal viscosity: |
|
150 cSt, 40 °C ± 3 K |
|
MW = measured value |
|
MEW = Final value of the measuring range |
|
| Pack quantity |
1 pcs. |
Electrical connection
| Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |