Datasheet
| Presentation | High density, double-conversion on-line power protection with scalable runtime. |
|---|---|
| Lead time | Usually in Stock |
Run time for load
W Enter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.
Min-max: 150-1500 W
|
|
|---|---|
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.
|
|
| Main Input Voltage | 230 V |
| Other Input Voltage | 220 V 240 V |
| Main Output Voltage | 230 V |
| Other Output Voltage | 220 V 240 V |
| rated power in W | 1500 W |
| Rated power in VA | 1500 VA |
| Input Connection Type | IEC 60320 C14 |
| output connection type | 6 IEC 60320 C13 |
| Number of rack unit | 2U |
| Cable length | 1.83 m |
| Number of cables | 1 |
| Battery type | Lead-acid battery |
| Provided equipment | CD with software Communication cable Documentation CD Installation guide Rack mounting hardware Rack mounting brackets Rack mounting support rails USB cable Warranty card |
| Run Time | View Runtime Graph |
|---|---|
| Number of battery filled slots | 1 |
| Number of battery free slots | 0 |
| Battery recharge time | 3 h |
| Number of battery replacement quantity | 1 |
| Battery charger power | 108 W rated |
| Battery power in VAH | 324 VAh runtime |
| Battery life | 3…5 year(s) |
| Replacement battery | APCRBC155 |
| Battery option | SRT48RMBP 1 972 VAh SRT48RMBP 2 1620 VAh SRT48RMBP 3 2268 VAh SRT48RMBP 4 2916 VAh SRT48RMBP 5 3564 VAh SRT48RMBP 6 4212 VAh SRT48RMBP 8 5508 VAh SRT48RMBP 10 6804 VAh |
| Extended runtime | 1 |
| product web sub-family | High density |
|---|---|
| Number of power module free slots | 0 |
| Number of power module filled slots | 0 |
| Redundant | No |
| Colour | Black |
|---|---|
| Height | 8.5 cm |
| Width | 43.2 cm |
| Depth | 50.5 cm |
| Net weight | 21 kg |
| Mounting preference | No preference |
| Mounting mode | Rack-mounted |
| Two post mountable | 0 |
| USB compatible | Yes |
| Mounting position | Horizontal |
| Network frequency | 40…70 Hz auto-sensing |
|---|---|
| Input voltage limits | 100…275 V 40% load 176…275 V full load |
| Maximum configurable power in W | 1500 W |
|---|---|
| Harmonic distortion | Less than 2 % |
| Output frequency | 50/60 Hz +/- 3 Hz sync to mains |
| Crest factor | 3 : 1 |
| UPS type | Double conversion online |
| Wave type | Sine wave |
| bypass type | Built-in bypass |
| Maximum configurable power in VA | 1500 VA |
| Product certifications | CE EAC |
|---|---|
| Standards | EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018 |
| Ambient air temperature for operation | 0…40 °C |
|---|---|
| Relative humidity | 0…95 % non-condensing |
| Operating altitude | 0…10000 ft |
| Ambient air temperature for storage | -20…50 °C |
| Storage Relative Humidity | 0…95 % non-condensing |
| Storage altitude | 0.00…15240.00 m |
| Acoustic level | 50 dBA |
| heat dissipation | 317 Btu/h |
| IP degree of protection | IP20 |
| Free slots | 1 |
|---|---|
| Alarm | Audible and visible alarms : prioritized by severity |
| Emergency power off | Yes |
| Surge energy rate | 432 J |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 24.6 cm |
| Package 1 Width | 74.9 cm |
| Package 1 Length | 59.4 cm |
| Package 1 Weight | 29.6 kg |
| Warranty | 3 years repair or replace (excluding battery) and 2 years for battery |
|---|