Schneider LV433223

0.00

The price is not final. Please check with the manager!

Schneider Electric Circuit breaker, ComPact NSX100HB2, 100kA/690VAC, TMD trip unit 50A, 4 poles 4d

Ask a Question

Datasheet

Main
RangeComPact
Product nameComPact NSX
Range of productComPact NSX100…250
Device short nameNSX100HB2
Product or component typeCircuit breaker
Device applicationDistribution
Number of poles4P
Protected poles description4t
Neutral positionLeft
[In] rated current50 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelHB2 100 kA 690 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
Mounting supportBackplate
upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating50 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7…1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
15 s at 6 x Ir
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range500 A
Short-time protection delay adjustment type tsdFixed
Earth-leakage protectionWithout
Neutral protection settings1 x Ir (4t)
Number of slots for electrical auxiliaries5 slot(s)
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.4 kg
Environment
StandardsEN/IEC 60947
Product certificationsCCC
Marine
EAC
Overvoltage categoryClass II
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0…2000 m without derating
2000 m…5000 m with derating