Datasheet
Range | ComPact |
---|---|
Product name | ComPact NSX DC |
Range of product | ComPact NSX630…1200 DC |
Device short name | NSX1200 DC |
Product or component type | Circuit breaker |
Device application | Distribution |
Number of poles | 2P |
Protected poles description | 2t |
[In] rated current | 1200 A at 40 °C |
[Ue] rated operational voltage | 600 V DC |
Network type | DC |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 50 kA Icu at 300 V DC 1P conforming to IEC 60947-2 50 kA Icu at 600 V DC 2P conforming to IEC 60947-2 |
Performance level | N 50 kA 600 V DC |
Trip unit name | TM-DC |
Trip unit technology | Thermal-magnetic |
Control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 600 V DC conforming to IEC 60947-2 |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 12.5 kA at 600 V DC conforming to IEC 60947-2 |
Mechanical durability | 5000 cycles |
Electrical durability | 1000 cycles at 600 V In 2000 cycles at 600 V In/2 |
Mounting support | Backplate |
upside connection | Front |
Downside connection | Front |
Connection pitch | 45 mm |
Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
Trip unit rating | 1200 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
[Ir] long-time protection pick-up adjustment range | 0.7…1 x In |
Long-time protection delay adjustment type tr | Fixed |
Short-time protection pick-up adjustment type Isd | Adjustable |
[Isd] Short-time protection pick-up adjustment range | 2.5…5 x In |
Short-time protection delay adjustment type tsd | Fixed |
Earth-leakage protection | Without |
Number of slots for electrical auxiliaries | 6 slot(s) |
Width (W) | 185 mm |
Height (H) | 350 mm |
Depth (D) | 110 mm |
Net weight | 9.4 kg |
Standards | EN/IEC 60947 |
---|---|
Product certifications | CCC EAC Marine |
Overvoltage category | Class II |
Electrical shock protection class | Class II |
Pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Relative humidity | 0…95 % |
Operating altitude | 0…2000 m without derating 2000 m…5000 m with derating |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |