Main
Range EasyPact
Product name MVS12N
Device short name MVS12N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
[In] rated current 1250 A at 40 °C
Network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET6G
Trip unit technology Electronic
Trip unit rating 1250 A
Complementary
Network frequency 50/60 Hz
Control type Manually operated
Mounting mode Drawout
Mounting support Base plate
Rail
Connection position Horizontal
Vertical
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Circuit breaker CT rating 1250 A
Breaking capacity 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 50 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making capacity 105 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 50 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LSIG
Protection type Short time short-circuit protection
Earth fault
Instantaneous short-circuit protection
Overload protection (long time)
Fault indication Short-circuit
Earth fault
Overload
Internal fault
Long time pick-up adjustment type Ir Adjustable 9 settings
long time pick-up adjustment range 0.4…1 x In
long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5…10 x Ir
Short-time delay adjustment type Adjustable 5 settings
[tsd] short-time delay adjustment range 100…400 ms
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range Off
2…15 x In
Ground-fault pick-up adjustment type Adjustable 9 settings
Ground-fault time delay adjustment type -tg Adjustable 5 settings
[tg] ground-fault time delay adjustment range 100…400 ms
[Ig] ground-fault pick-up adjustment range 500…1200 A
Zone selective interlocking ZSI With
current sensor rating range 400/2000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 439 mm
Width 441 mm
Depth 395 mm
Net weight 70 kg
Environment
Standards IEC 60947-2
Product certifications GOST
CCC
CCS
IEC
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
Ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 42.0 cm
Package 1 Width 35.0 cm
Package 1 Length 50.0 cm
Package 1 Weight 38.0 kg
Contractual warranty
Warranty 18 months