Schneider LV847128

0.00

The price is not final. Please check with the manager!

Schneider Electric Circuit breaker frame, MasterPact MTZ1 08H2, 800A, 50kA/440VAC 50/60Hz (Icu), 4P, fixed, without control unit

Contact Sales

Datasheet

Main
Range MasterPacT
Product name MasterPact MTZ1
Device short name MTZ1 08 H2
Product or component type Circuit breaker
Device application Power distribution protection
Poles description 4P
Neutral position Left
Control unit Without control unit
[In] rated current 800 A at 40 °C
Performance type H2 50 kA 440 V AC
[Ue] rated operational voltage 690 V AC 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Selectivity category Category B
Control type Push-button
Mounting mode Fixed
Complementary
[Icu] rated ultimate short-circuit breaking capacity 50 kA at 220/415 V AC 50/60 Hz
50 kA at 440 V AC 50/60 Hz
42 kA at 500/525 V AC 50/60 Hz
42 kA at 660/690 V AC 50/60 Hz
[Ics] rated service breaking capacity 50 kA at 220/415 V AC 50/60 Hz
50 kA at 440 V AC 50/60 Hz
42 kA at 500/525 V AC 50/60 Hz
42 kA at 660/690 V AC 50/60 Hz
[Icw] rated short-time withstand current 42 kA 0.5 s
42 kA 1 s
24 kA 3 s
[Icm] rated short-circuit making capacity 105 kA 220/415 V AC at 50/60 Hz
105 kA 440 V AC at 50/60 Hz
88 kA 500/525 V AC at 50/60 Hz
88 kA 660/690 V AC at 50/60 Hz
Integrated instantaneous protection (DIN in kA peak) 81…99 kA
Sensor rating 400 A
630 A
800 A
[Ui] rated insulation voltage 1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 12 kV
Power dissipation in W 50 W
Maximum breaking time 25 ms
Maximum closing response time 50 ms
Mounting support Rails
Base plate
upside connection Front
Rear
Downside connection Front
Rear
Connection pitch 70 mm
Mechanical durability 12500 cycles with periodic preventive maintenance
Electrical durability 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3
AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Height 301 mm
Width 346 mm
Depth 209 mm
Net weight 18 kg
Standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-2 Annex H
IEC 61557-12
Product certifications CE
IECEE CB Scheme
Environment
IP degree of protection IP30 conforming to EN 60529
Pollution degree 3 conforming to IEC 60947-1
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…85 °C
Operating altitude 0…2000 m without derating
2000…5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 40.0 cm
Package 1 Width 40.0 cm
Package 1 Length 30.0 cm
Package 1 Weight 21.506 kg

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews