Schneider Electric Circuit breaker frame, MasterPact MTZ2 32H3, 3200A, 150kA/440VAC 50/60Hz (Icu), 3P, drawout, without control unit

Ask a Question

Datasheet

Main
RangeMasterPacT
Product nameMasterPact MTZ2
Device short nameMTZ2 32 H3
Product or component typeCircuit breaker
Device applicationPower distribution protection
Poles description3P
Control unitWithout control unit
[In] rated current3200 A at 40 °C
Performance typeH3 150 kA 440 V AC
[Ue] rated operational voltage440 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Selectivity categoryCategory B
Control typePush-button
Mounting modeDrawout
Complementary
[Icu] rated ultimate short-circuit breaking capacity150 kA at 220/415 V AC 50/60 Hz
150 kA at 440 V AC 50/60 Hz
130 kA at 500/525 V AC 50/60 Hz
100 kA at 660/690 V AC 50/60 Hz
[Ics] rated service breaking capacity150 kA at 220/415 V AC 50/60 Hz
150 kA at 440 V AC 50/60 Hz
130 kA at 500/525 V AC 50/60 Hz
100 kA at 660/690 V AC 50/60 Hz
[Icw] rated short-time withstand current66 kA 0.5 s
66 kA 1 s
66 kA 3 s
[Icm] rated short-circuit making capacity330 kA 220/415 V AC at 50/60 Hz
330 kA 440 V AC at 50/60 Hz
286 kA 500/525 V AC at 50/60 Hz
220 kA 660/690 V AC at 50/60 Hz
Integrated instantaneous protection (DIN in kA peak)135…165 kA
Sensor rating1600 A
2000 A
2500 A
3200 A
[Ui] rated insulation voltage1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
Power dissipation in W670 W
Maximum breaking time25 ms
Maximum closing response time70 ms
Mounting supportRails
Base plate
upside connectionFront
Rear
Downside connectionFront
Rear
Connection pitch115 mm
Mechanical durability20000 cycles with periodic preventive maintenance
Electrical durability1250 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
1250 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2
HeightDrawout circuit breaker with chassis: 439 mm
Drawout circuit breaker without chassis: 300 mm
WidthDrawout circuit breaker with chassis: 441 mm
Drawout circuit breaker without chassis: 378 mm
DepthDrawout circuit breaker with chassis: 403 mm
Drawout circuit breaker without chassis: 300 mm
Net weight90 kg
StandardsEN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-2 Annex H
IEC 61557-12
Product certificationsCE
IECEE CB Scheme
Environment
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude0…2000 m without derating
2000…5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height30.5 cm
Package 1 Width29.5 cm
Package 1 Length37.5 cm
Package 1 Weight51.233 kg