Datasheet
Range | MasterPacT |
---|---|
Product name | MasterPact MTZ3 |
Device short name | MTZ3 63 H1 |
Product or component type | Circuit breaker |
Device application | Power distribution protection |
Poles description | 4P |
Neutral position | Right |
Control unit | Without control unit |
[In] rated current | 6300 A at 40 °C |
Performance type | H1 100 kA 440 V AC |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Selectivity category | Category B |
Control type | Push-button |
Mounting mode | Drawout |
[Icu] rated ultimate short-circuit breaking capacity | 100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz 100 kA at 660/690 V AC 50/60 Hz |
---|---|
[Ics] rated service breaking capacity | 100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz 100 kA at 660/690 V AC 50/60 Hz |
[Icw] rated short-time withstand current | 100 kA 0.5 s 100 kA 1 s 100 kA 3 s |
[Icm] rated short-circuit making capacity | 220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz 220 kA 500/525 V AC at 50/60 Hz 220 kA 660/690 V AC at 50/60 Hz |
Sensor rating | 3200 A 4000 A 5000 A 6300 A |
[Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 12 kV |
Power dissipation in W | 900 W |
Maximum breaking time | 25 ms |
Maximum closing response time | 80 ms |
Mounting support | Rails Base plate |
upside connection | Rear |
Downside connection | Rear |
Connection pitch | 230 mm |
Mechanical durability | 10000 cycles with periodic preventive maintenance |
Electrical durability | AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 |
Height | Drawout circuit breaker with chassis: 479 mm Drawout circuit breaker without chassis: 300 mm |
Width | Drawout circuit breaker with chassis: 1016 mm Drawout circuit breaker without chassis: 838 mm |
Depth | Drawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm |
Net weight | 300 kg |
Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12 |
Product certifications | CE IECEE CB Scheme |
IP degree of protection | IP30 conforming to EN 60529 |
---|---|
Pollution degree | 3 conforming to IEC 60947-1 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | 0…2000 m without derating 2000…5000 m with derating |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 60.0 cm |
Package 1 Width | 120.0 cm |
Package 1 Length | 50.0 cm |
Package 1 Weight | 133.324 kg |