Datasheet
Range | ClimaSys |
---|---|
Product name | ClimaSys CE |
Product or component type | Air-water exchanger |
mounting type | Sides of enclosure |
Cooling power | 2500 W |
Pressure | 5 bar for water |
---|---|
Pressure drop | 0.3 bar |
Water flow | Internal circuit: 500 l/h |
Flow rate | External circuit: 860 m3/h |
Control type | Thermostat |
Temperature setting range | 20…46 °C |
Ambient air temperature for operation | 1…70 °C outside the enclosure: 20…60 °C inside the enclosure: |
Controlled fluid | Water |
Fluid connection type | G 1/2 (female) |
Input voltage | 230 V 50/60 Hz |
[In] rated current | 0.33 A |
Power consumption in W | 80 W |
Height | 901 mm external: |
Width | 398 mm external: |
Depth | 137 mm external: |
Net weight | 19 kg |
Noise level | 58 dB conforming to EN/ISO 3746 |
Protection type | Thermal protection: T 2 A |
Material | Steel |
Colour | Grey (RAL 7035) |
IP degree of protection | IP55 conforming to IEC 60529 (on the internal circuit) IP55 conforming to IEC 60529 (on the external circuit) |
---|---|
Product certifications | CE |
Directives | 2004/108/EC – electromagnetic compatibility 2006/42/EC – machinery 2006/95/EC – low voltage directive |
Standards | EN 60204-1 EN 60335-1 EN/ISO 12100 EN 60335-2-40 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 16.3 cm |
Package 1 Width | 39.8 cm |
Package 1 Length | 90.1 cm |
Package 1 Weight | 19.0 kg |
Unit Type of Package 2 | P12 |
Number of Units in Package 2 | 7 |
Package 2 Height | 117.0 cm |
Package 2 Width | 80.0 cm |
Package 2 Length | 120.0 cm |
Package 2 Weight | 165.0 kg |