Datasheet
Range | ClimaSys |
---|---|
Product name | CU |
Product or component type | Cooling unit |
mounting type | Roof of enclosure |
Type of installation | Indoor |
Product destination | For enclosure |
Mounting mode | By screws |
Input voltage | 400 V 50/60 Hz |
Network number of phases | 3 phases |
Cooling power | 2900 W 50/60 Hz L35-L35 2250 W 50/60 Hz L35-L50 |
Height | 496 mm |
---|---|
Width | 797 mm |
Depth | 492 mm |
[In] rated current | 2.5 A |
Inrush current | 15.7 A |
Power consumption in W | 1210 W at 50/60 Hz, L35-L35 1450 W at 50/60 Hz, L35-L50 |
Energy efficiency ratio | 2.4 |
Control type | Electronic controller |
Temperature setting range | 20…50 °C |
Ambient air temperature for operation | 50 °C maximum: 20…46 °C inside the enclosure: 20…50 °C outside the enclosure: |
Noise level | 75 dB conforming to EN/ISO 3746 |
Pressure | 25 bar |
Flow rate | Internal circuit: 860 m3/h at 50/60 Hz External circuit: 3410 m3/h at 50/60 Hz |
Net weight | 83 kg |
Cooling gas type | R134a (1.2 kg) |
Type of filter | Optional external circuit filter |
Protection type | Thermal protection: T 6 A Short-circuit protection (magnetic): |
Material | Steel |
Colour | Grey (RAL 7035) |
Product certifications | CE |
---|---|
Directives | 2006/95/EC – low voltage directive 2004/108/EC – electromagnetic compatibility 2006/42/EC – machinery |
Standards | EN 60204-1 EN 60335-2-40 EN 60335-1 EN 378 EN/ISO 12100 |
IP degree of protection | IP34 conforming to IEC 60529 (on the external circuit) IP54 conforming to IEC 60529 (on the internal circuit) |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 49.2 cm |
Package 1 Width | 49.6 cm |
Package 1 Length | 79.7 cm |
Package 1 Weight | 83.0 kg |
Unit Type of Package 2 | P12 |
Number of Units in Package 2 | 2 |
Package 2 Height | 152.0 cm |
Package 2 Width | 80.0 cm |
Package 2 Length | 120.0 cm |
Package 2 Weight | 213.0 kg |