Datasheet
Lead time | Usually Ships within 4 Weeks |
---|
Range | ClimaSys |
---|---|
Product name | CU |
Product or component type | Cooling unit |
mounting type | Side |
Type of installation | Indoor |
Product destination | For enclosure |
Mounting mode | By screws |
Input voltage | 230 V 50/60 Hz |
Network number of phases | 1 phase |
Cooling power | 1000 W 50/60 Hz L35-L35 790 W 50/60 Hz L35-L50 |
Height | 783 mm |
---|---|
Width | 348 mm |
Depth | 215 mm |
[In] rated current | 3 A |
Inrush current | 10.5 A |
Power consumption in W | 570 W at 50/60 Hz, L35-L35 650 W at 50/60 Hz, L35-L50 |
Energy efficiency ratio | 1.8 |
Control type | Electronic controller |
Temperature setting range | 20…55 °C at 50 Hz 20…50 °C at 60 Hz |
Ambient air temperature for operation | 20…46 °C inside the enclosure: 55 °C maximum: 20…55 °C at 50 Hz outside the enclosure: 20…50 °C at 60 Hz outside the enclosure: |
Noise level | 65 dB conforming to EN/ISO 3746 |
Pressure | 25 bar |
Flow rate | Internal circuit: 330 m3/h at 50/60 Hz External circuit: 570 m3/h at 50/60 Hz |
Net weight | 28 kg |
Cooling gas type | R134a (0.23 kg) |
Type of filter | Optional external circuit filter |
Protection type | Thermal protection: T 6 A Short-circuit protection (magnetic): |
Material | Steel |
Colour | Grey (RAL 7035) |
Product certifications | CE |
---|---|
Directives | 2004/108/EC – electromagnetic compatibility 2006/42/EC – machinery 2006/95/EC – low voltage directive |
Standards | EN 60335-2-40 EN 60335-1 EN 378 EN/ISO 12100 EN 60204-1 |
IP degree of protection | IP55 conforming to IEC 60529 (on the internal circuit) IP34 conforming to IEC 60529 (on the external circuit) |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 33.0 cm |
Package 1 Width | 40.0 cm |
Package 1 Length | 85.5 cm |
Package 1 Weight | 31.0 kg |
Unit Type of Package 2 | P12 |
Number of Units in Package 2 | 6 |
Package 2 Height | 103.0 cm |
Package 2 Width | 80.0 cm |
Package 2 Length | 120.0 cm |
Package 2 Weight | 211.0 kg |