Datasheet
| Range | ClimaSys |
|---|---|
| Product name | CU |
| Product or component type | Cooling unit |
| mounting type | Side |
| Type of installation | Indoor |
| Product destination | For enclosure |
| Mounting mode | By screws |
| Input voltage | 400…440 V 50/60 Hz |
| Network number of phases | 2 phases |
| Cooling power | 1000 W 50/60 Hz L35-L35 790 W 50/60 Hz L35-L50 |
| Height | 783 mm |
|---|---|
| Width | 348 mm |
| Depth | 215 mm nominal: 273 mm total: |
| [In] rated current | 2 A |
| Inrush current | 8 A |
| Power consumption in W | 590 W at 50/60 Hz, L35-L35 670 W at 50/60 Hz, L35-L50 |
| Energy efficiency ratio | 1.7 |
| Control type | Electronic controller |
| Temperature setting range | 20…50 °C |
| Ambient air temperature for operation | 50 °C maximum: 20…46 °C inside the enclosure: 20…50 °C outside the enclosure: |
| Noise level | 65 dB conforming to EN/ISO 3746 |
| Pressure | 25 bar |
| Flow rate | Internal circuit: 330 m3/h at 50/60 Hz External circuit: 570 m3/h at 50/60 Hz |
| Net weight | 29 kg |
| Cooling gas type | R134a (0.23 kg) |
| Type of filter | Optional external circuit filter |
| Protection type | Thermal protection: T 4 A Short-circuit protection (magnetic): |
| Material | Steel |
| Colour | Grey (RAL 7035) |
| Product certifications | CE |
|---|---|
| Directives | 2006/95/EC – low voltage directive 2004/108/EC – electromagnetic compatibility 2006/42/EC – machinery |
| Standards | EN 60335-1 EN/ISO 12100 EN 378 EN 60204-1 EN 60335-2-40 |
| IP degree of protection | IP55 conforming to IEC 60529 (on the internal circuit) IP34 conforming to IEC 60529 (on the external circuit) |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 21.5 cm |
| Package 1 Width | 34.8 cm |
| Package 1 Length | 78.3 cm |
| Package 1 Weight | 29.0 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 120.5 cm |
| Package 2 Width | 80.0 cm |
| Package 2 Length | 120.0 cm |
| Package 2 Weight | 236.0 kg |