Datasheet
| Range | ClimaSys |
|---|---|
| Product name | CU |
| Product or component type | Cooling unit |
| mounting type | Side |
| Type of installation | Indoor |
| Product destination | For enclosure |
| Mounting mode | By screws |
| Input voltage | 400 V 50/60 Hz |
| Network number of phases | 3 phases |
| Cooling power | 3850 W 50/60 Hz L35-L35 2870 W 50/60 Hz L35-L50 |
| Height | 1270 mm |
|---|---|
| Width | 500 mm |
| Depth | 336 mm |
| [In] rated current | 3.6 A |
| Inrush current | 18 A |
| Power consumption in W | 1780 W at 50/60 Hz, L35-L35 2050 W at 50/60 Hz, L35-L50 |
| Energy efficiency ratio | 2.2 |
| Control type | Electronic controller |
| Temperature setting range | 20…50 °C |
| Ambient air temperature for operation | 50 °C maximum: 20…46 °C inside the enclosure: 20…50 °C outside the enclosure: |
| Noise level | 70 dB conforming to EN/ISO 3746 |
| Pressure | 25 bar |
| Flow rate | Internal circuit: 1450 m3/h at 50/60 Hz External circuit: 1450 m3/h at 50/60 Hz |
| Net weight | 85 kg |
| Cooling gas type | R134a (1.14 kg) |
| Type of filter | Optional external circuit filter |
| Protection type | Thermal protection: T 8 A Short-circuit protection (magnetic): |
| Material | Steel |
| Colour | Grey (RAL 7035) |
| Product certifications | CE |
|---|---|
| Directives | 2004/108/EC – electromagnetic compatibility 2006/42/EC – machinery 2006/95/EC – low voltage directive |
| Standards | EN 60335-2-40 EN 378 EN 60204-1 EN/ISO 12100 EN 60335-1 |
| IP degree of protection | IP55 conforming to IEC 60529 (on the internal circuit) IP34 conforming to IEC 60529 (on the external circuit) |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 33.6 cm |
| Package 1 Width | 50.0 cm |
| Package 1 Length | 127.0 cm |
| Package 1 Weight | 85.0 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 160.0 cm |
| Package 2 Width | 80.0 cm |
| Package 2 Length | 120.0 cm |
| Package 2 Weight | 225.0 kg |