Datasheet
Range | TeSys |
---|---|
Range of product | TeSys F |
Product or component type | Contactor |
Device short name | LC1F |
Contactor application | Resistive load |
Utilisation category | AC-1 |
Poles description | 3P |
[Ue] rated operational voltage | <= 460 V DC <= 690 V AC 50/60 Hz |
[Uc] control circuit voltage | 220 V AC 40…400 Hz |
[Ie] rated operational current | 1260 A (at <40 °C) AC-1 |
[Uimp] rated impulse withstand voltage | 8 kV |
---|---|
[Ith] conventional free air thermal current | 1260 A (at 40 °C) |
Rated breaking capacity | 1890 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 3000 A 40 °C – 3 min 8000 A 40 °C – 10 s 5200 A 40 °C – 30 s 4000 A 40 °C – 1 min 2000 A 40 °C – 10 min |
Associated fuse rating | 1000 A gG at <= 440 V |
Average impedance | 0.12 mOhm – Ith 1260 A 50 Hz |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
Power dissipation per pole | 120 W AC-1 |
Overvoltage category | III |
power pole contact composition | 3 NO |
Control circuit voltage limits | Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C) Drop-out: 0.25…0.5 Uc 40…400 Hz (at 55 °C) |
Inrush power in VA | 1650 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
Hold-in power consumption in VA | 22 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
Maximum operating rate | 1200 cyc/h 55 °C |
Operating time | 40…80 ms closing 100…200 ms opening |
Connections – terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) – busbar cross section: 100 x 5 mm Power circuit: bolted connection |
Tightening torque | Control circuit: 1.2 N.m Power circuit: 58 N.m |
Mounting support | Plate |
Heat dissipation | 20 W |
Standards | EN 60947-4-1 IEC 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1 |
Product certifications | CB CSA CCC cETLus UKCA |
Compatibility code | LC1F |
Control circuit type | AC at 40…400 Hz |
Protective treatment | TH |
---|---|
Ambient air temperature for operation | -5…40 °C |
Ambient air temperature for storage | -60…80 °C |
Permissible ambient air temperature around the device | -40…60 °C |
Height | 338 mm |
Width | 309 mm |
Depth | 255 mm |
Operating altitude | 3000 m without derating |
Net weight | 19 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 33.0 cm |
Package 1 Width | 37.0 cm |
Package 1 Length | 44.0 cm |
Package 1 Weight | 20.1 kg |
Warranty | 18 months |
---|