Datasheet
| Range | TeSys |
|---|---|
| Product name | TeSys F |
| Product or component type | Contactor |
| Device short name | LC1F |
| Contactor application | Resistive load Motor control |
| Utilisation category | AC-3 AC-1 |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | <= 440 V AC 50/60 Hz |
| [Ie] rated operational current | 1250 A (at <40 °C) at <= 440 V AC AC-1 1000 A (at <55 °C) at <= 440 V AC AC-3 |
| [Uc] control circuit voltage | 110…500 V AC 40…400 Hz with LX1/LX9 coil 110…440 V DC with LX4 coil |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 1250 A (at 40 °C) |
| Irms rated making capacity | 10 kA AC conforming to IEC 60947-4-1 |
| Rated breaking capacity | 8 kA conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 7500 A 40 °C – 30 s 5500 A 40 °C – 1 min 4200 A 40 °C – 3 min 3000 A 40 °C – 10 min 10000 A 40 °C – 10 s |
| Associated fuse rating | 2000 A gG at <= 440 V |
| Average impedance | 0.1 mOhm – Ith 1250 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| Power dissipation per pole | 200 W AC-1 |
| Control circuit voltage limits | Operational: 0.85…1.1 Uc AC 40…400 Hz with LX1/LX9 coil Drop-out: 0.3…0.5 Uc AC 40…400 Hz with LX1/LX9 coil Operational: 0.85…1.1 Uc DC with LX4 coil Drop-out: 0.2…0.35 Uc DC with LX4 coil |
| Heat dissipation | 18 W |
| Operating time | 40…75 ms closing for with LX1/LX9 coil 100…170 ms opening for with LX1/LX9 coil 50…60 ms closing for with LX4 coil 45…60 ms opening for with LX4 coil |
| Mounting support | Plate |
| Standards | EN 60947-4-1 IEC 60947-4-1 EN 60947-1 IEC 60947-1 |
| Product certifications | CB CSA CCC UKCA |
| Connections – terminals | Power circuit: bar 4 cable(s) Power circuit: bar 3 cable(s) Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² |
| Tightening torque | Power circuit: 58 N.m Control circuit: 1.2 N.m |
| Mechanical durability | 0.5 Mcycles |
| Inrush power in VA | 1600…2400 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 2000…2200 VA (at 20 °C)with LX4 coil |
| Hold-in power consumption in VA | 29…37 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 8…10 VA (at 20 °C)with LX4 coil |
| Maximum operating rate | 600 cyc/h 55 °C |
| Compatibility code | LC1F |
| Power range | 315 kW at 220…230 V 3 phases 560 kW at 380…400 V 3 phases 630 kW at 415 V 3 phases 670 kW at 440 V 3 phases |
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
|---|---|
| Protective treatment | TH |
| Ambient air temperature for operation | -5…40 °C |
| Ambient air temperature for storage | -60…80 °C |
| Permissible ambient air temperature around the device | -40…60 °C |
| Operating altitude | 3000 m without derating |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5…300 Hz Vibrations contactor closed: 4 Gn, 5…300 Hz Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms) Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms) |
| Height | 332 mm |
| Width | 438 mm |
| Depth | 238.6 mm |
| Net weight | 31 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 36.1 cm |
| Package 1 Width | 48.3 cm |
| Package 1 Length | 60.3 cm |
| Package 1 Weight | 23 kg |
| Warranty | 18 months |
|---|