Schneider LC1F7804

0.00

The price is not final. Please check with the manager!

Schneider Electric contactor, TeSys F, 4P(4NO), AC-1, <=440V 1600A with coil LX1/LX9 110…500V AC 40/400Hz, LX4 110...440V DC

Ask a Question

Datasheet

Main
RangeTeSys
Product nameTeSys F
Product or component typeContactor
Device short nameLC1F
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
power pole contact composition4 NO
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz
<= 460 V DC
[Ie] rated operational current1600 A (at <40 °C) at <= 440 V AC AC-1
Complementary
[Uc] control circuit voltage110…500 V AC 40…400 Hz with LX1/LX9 coil
48…440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current1600 A (at 40 °C)
Irms rated making capacity7800 A AC conforming to IEC 60947-4-1
Rated breaking capacity6240 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current3000 A 40 °C – 3 min
6250 A 40 °C – 10 s
5600 A 40 °C – 30 s
4600 A 40 °C – 1 min
2200 A 40 °C – 10 min
Associated fuse rating800 A aM at <= 440 V
1600 A gG at <= 440 V
Average impedance0.1 mOhm – Ith 1600 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
Power dissipation per pole250 W AC-1
Control circuit voltage limitsOperational: 0.85…1.1 Uc AC 40…400 Hz with LX1/LX9 coil
Drop-out: 0.2…0.4 Uc AC 40…400 Hz with LX1/LX9 coil
Operational: 0.85…1.1 Uc DC with LX4 coil
Drop-out: 0.2…0.4 Uc DC with LX4 coil
Heat dissipation22 W
Operating time40…80 ms closing for with LX1/LX9 coil
130…230 ms opening for with LX1/LX9 coil
70…80 ms closing for with LX4 coil
100…130 ms opening for with LX4 coil
Mounting supportPlate
StandardsIEC 60947-1
IEC 60947-4-1
EN 60947-1
JIS C8201-4-1
EN 60947-4-1
Product certificationsUL
LROS (Lloyds register of shipping)
RINA
DNV
CCC
BV
CB
ABS
UKCA
Connections – terminalsPower circuit: bar 2 cable(s) – busbar cross section: 100 x 5 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Tightening torquePower circuit: 58 N.m
Control circuit: 1.2 N.m
Mechanical durability5 Mcycles
Inrush power in VA1900…2300 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
1960…2420 VA (at 20 °C)with LX4 coil
Hold-in power consumption in VA44…55 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
42…52 VA (at 20 °C)with LX4 coil
Maximum operating rate600 cyc/h 55 °C
Compatibility codeLC1F
Environment
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
Protective treatmentTH
Ambient air temperature for operation-5…55 °C
Ambient air temperature for storage-60…80 °C
Permissible ambient air temperature around the device-40…70 °C
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2.5 Gn, 5…300 Hz
Vibrations contactor closed: 5.5 Gn, 5…300 Hz
Shocks contactor open: 5 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
Height434 mm
Width862 mm
Depth255 mm
Net weight48 kg
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height41.0 cm
Package 1 Width115.0 cm
Package 1 Length44.0 cm
Package 1 Weight47.5 kg
Unit Type of Package 2PAL
Number of Units in Package 22
Package 2 Height85.0 cm
Package 2 Width120.0 cm
Package 2 Length80.0 cm
Package 2 Weight142.0 kg
Contractual warranty
Warranty18 months