Datasheet
| Range of product | Easergy T300 |
|---|---|
| Device short name | HU250 |
| Product or component type | Communication gateway |
|---|---|
| Communication port protocol | DNP3 serial and TCP master station/outstation Modbus serial and TCP client/server IEC 61850-8-1 controlling/controlled station IEC 60870-5-104 controlling/controlled station IEC 60870-5-101 controlled station |
| Communication port support | ETHERNET 4 RJ45 RS232/485 Modbus/ASCII 1 RJ45 RS485/RS232 1 RJ45 3G/4G 1 SMA |
| Data recording | Event logs 4 data logs 1 ms time stamps 500000 events Sequence of event recording |
| Memory capacity | 16 MB |
| Time synchronisation protocol | NTP SNTP GPS |
| Synchronisation time between inputs | 1 ms |
| Control type | Illuminated push-button status: |
| Communication service | Web server local WiFi: Web server local Ethernet: Web server remote WAN: |
| web services | Event log Alarm Operating/Status report Assistance in commissioning and operating the installation Security/authority verification Reports and diagrams |
| Programming language | Calculation formula ST (structured text) IL (instruction list) LD (ladder) FBD (function block diagram) SFC (sequential function chart) |
| Number of inputs | 6 digital multi-purpose conforming to IEC 61131-2 type 3 2 digital remote control 2 analog measure temperature |
| Number of outputs | 2 digital (relay) multi-purpose: |
| [Us] rated supply voltage | 12…48 V DC +/- 20 % |
| Power consumption in VA | 3 VA |
| language | Multi-language |
|---|---|
| Electromagnetic compatibility | Electrical fast transient/burst immunity test – test level: level 4 criteria A conforming to IEC 61000-4-4 Conducted RF disturbances – test level: level 3 criteria A conforming to IEC 61000-4-6 Conducted disturbance emission – test level: level 4 criteria A conforming to IEC 61000-4-16 100 kHz damped oscillating wave – test level: level 3 criteria A conforming to IEC 61000-4-12 Radiated radio-frequency electromagnetic field immunity test – test level: level 4 criteria A conforming to IEC 61000-4-3 Immunity to voltage dips criteria A conforming to IEC 61000-4-29 Electrostatic discharge – test level: level 4 criteria B conforming to IEC 61000-4-2 Surge immunity test – test level: level 3 criteria A conforming to IEC 61000-4-5 Magnetic field at power frequency – test level: level 5 criteria B conforming to IEC 61000-4-8 Conducted and radiated emissions class A conforming to EN 55022 |
| Fixing mode | Clip-in (DIN rail) |
| Type of installation | Indoor Outdoor in cabinet |
| IP degree of protection | IP2X body: conforming to IEC 60529 IP4X front: conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Relative humidity | 5…95 % conforming to IEC 60068-2-30 |
| Mechanical robustness | Vibrations 10…2000 Hz 1 gn 10 cycles conforming to IEC 60068-2-6 Bumps 10 gn 16 ms 1000 bumps non energized conforming to IEC 60068-2-29 Shocks 11 ms 3 pulses in operation conforming to IEC 60068-2-27 |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 2000 m |
| Product certifications | CE |
| Standards | IEC 60255-27 |
| Height | 140 mm |
| Width | 90 mm |
| Depth | 140 mm |
| Net weight | 0.55 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.900 cm |
| Package 1 Width | 19.100 cm |
| Package 1 Length | 19.800 cm |
| Package 1 Weight | 765.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 9 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 7.277 kg |