Datasheet
Range | Exiway Dicube |
---|---|
Product name | Exiway Dicube Smartcontrol |
Product or component type | Control unit with line controller module |
Device application | Light control Diagnosis capabilities Battery monitoring of the luminaires |
Device short name | Exiway Smart Control LC |
Range compatibility | Exiway (Exiway Smartduo DiCube) emergency light fitting Exiway (Exiway Smartled Dicube) emergency light fitting Exiway (Exiway Smartbeam DiCube) emergency light fitting Exiway (Exiway Smartexit Dicube) emergency light fitting |
Function | Addressable |
function available | Configure over bluetooth With integrated web server |
Operating mode | Manual or automatic |
communication port protocol | Bluetooth Ethernet Serial link DALI |
Device composition | I/O terminals HMI push button |
---|---|
Control type | By software By mobile application Remote control 2 x test button |
web services | Web server |
language | English Italian |
[Ue] rated operational voltage | 230 V AC 50…60 Hz |
number of line controlled | 2 |
Number of devices | 2 serial link 128 DALI |
Physical interface | 1 x RS485 2 x RS232 1 x Ethernet 4 x screw block terminal |
Ethernet service | Configuration via web server |
Number of outputs | 2 relay |
Output voltage | 150 V DC for relay output 230 V AC for relay output 16 V 5…235 mA for line control connection to the luminaires |
Number of inputs | 2 contact |
Input voltage | Input: 3 V DC, 0.2 mA Auxiliary input: 230 V AC, 2.5 mA |
Clamping connection capacity | 2 x 1.5 mm²for inputs 2 x 1…2.5 mm²per line |
Maximum of controlled luminaires by a control unit | 128 |
Communication network type | Bluetooth (2400000…2483500 kHz), 1 mW at 30 m |
Number of batteries | 1 x 3 V Li-MnO2 (Lithium-Manganese Dioxide) |
Battery size | CR2477M |
Local signalling | LED green for control unit connected to at least one line controller LED red for no communication with line controller LED green, flashing for Ethernet network status (RUN) LED red for Ethernet port fault (ERR) LED green for luminaires status : OK LED green, flashing for test mode LED red for faulty luminaire LED red, flashing for luminaire inhibition LED blue for bluetooth LED red for power (PWR OK) LED red, stop or suppress for power supply (OFF) LED red, fast flashing for DALI communication LED red for lights on LED red, stop or suppress for lights off LED red, slow flashing for adressing terminals LED red for fault LED red, stop or suppress for defect LED red, slow flashing for identification of addressed devices LED red, fast flashing for broadcasting identification LED red, slow flashing for ACT (activity on Line A) LED red, slow flashing for ACT (activity on Line B) |
Software designation | EcoStruxure emergency lighting expert |
device mounting | DIN rail |
Electrical insulation class | Class II |
Relative humidity | 5…85 % |
Pollution degree | 2 |
IP degree of protection | IP20 |
atmospheric-corrosivity category | C3 |
Height | Control unit: 85 mm Line controller: 92 mm |
Width | Control unit: 90 mm Line controller: 72 mm |
Depth | Control unit: 69.5 mm Line controller: 63 mm |
Directives | 2014/53/EU – radio equipment directive |
Net weight | 0.45 kg |
Standards | EN 55022 EN 55024 EN 61000-3-2 EN 61000-3-3 EN 60950 IEC/EN 62034 |
---|---|
Ambient air temperature for operation | 0…40 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 8.5 cm |
Package 1 Width | 7.0 cm |
Package 1 Length | 16.2 cm |
Package 1 Weight | 530.0 g |