Schneider LV865307

0.00

The price is not final. Please check with the manager!

Schneider Electric MicroLogic 7.0X control unit, MasterPact MTZ1, drawout circuit breakers, LSIV protections

Ask a Question

Datasheet

Main
RangeMasterPacT
Device short nameMicroLogic 7.0 X
Product or component typeControl unit
Device applicationEquipment protection, monitoring and control
Circuit breaker applicationDistribution IEC standard
Range compatibilityMasterPact MTZ1 circuit breaker
Poles3P
4P
Protected poles description3P 3d
4P 3d
4P 3d + N/2
4P 4d
4P 3d + OSN
[Ue] rated operational voltage600 V AC, +/- 10 %
Network typeAC
Network frequency50/60 Hz
Trip unit technologyElectronic
Trip unit protection functionsLSIV
Protection typeOverload protection (long time) conforming to ANSI 49
Instantaneous short-circuit protection conforming to ANSI 50
Short time short-circuit protection conforming to ANSI 51
Earth-leakage protection conforming to ANSI 51G
Trip unit rating400 A
630 A
800 A
1000 A
1250 A
1600 A
Complementary
Mounting modeDrawout
Neutral protection setting1 x Ir (4P 4d)
0.5 x Ir (4P 3d + N/2)
1.6 x Ir (4P 3d + OSN)
No protection (4P 3d)
[Ir] long time pick-up adjustment range0.4…1 x In adjustable in step of 1 A
long time delay adjustment typeAdjustable in step of 0.5 s
[tr] long-time delay adjustment range12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
Thermal memoryYes
[Isd] short-time pick-up adjustment range1.5…10 x Ir adjustable in step of 0.5 x Ir with embedded HMI
1.5…10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or MasterPact MTZ mobile app
Short-time delay adjustment typeAdjustable
[tsd] short-time delay adjustment range0.1…0.4 s I²t=on
0…0.4 s I²t=off
Instantaneous pick-up adjustment type IiAdjustable
[Ii] instantaneous pick-up adjustment range2…15 x In adjustable in step of 0.5 x In with embedded HMI
2…15 x In adjustable in step of 0.1 x In with Ecoreach software or MasterPact MTZ mobile app
Ii enable on/off
[li mode] instantaneous delay adjustment range0 ms in fast
20 ms in standard
Earth-leakage protectionWith
[IΔn] residual earth-leakage sensitive adjustment0.5…30 A adjustable in step of 0.1 A
Residual earth-leakage time delay adjustment typeAdjustable
[Δt] residual earth-leakage time delay adjustment60…800 ms resettable time
140…1000 ms break time
Zone selective interlocking ZSIWith
Network and machine diagnosis typeSystem (HMI) health state overview: circuit breaker health state
Contacts state: circuit breaker health state
MicroLogic service life: circuit breaker health state
Tripping cause indication: circuit breaker tripping cause
Identification card: diagnostic data
Configured alarms synthesis: diagnostic data
Monitored function: diagnostic data
Operation: diagnostic data
MicroLogic test: test
Protection test: test
Selectivity test: test
Trip context information: crisis management
Operation: advanced diagnostic
Breaker service life: circuit breaker health state
type of measurementPower meter
Energy managementMeasurement ,active, reactive and apparent energy
Measurement ,electrical network
Measurement ,energy
Metering typeCurrent I1, I2, I3, Iavg RMS
Neutral current IN RMS
Ground fault current Ig RMS
Voltage V12, V23, V31, VLLavg RMS
Voltage V1N, V2N, V3N, VLNavg RMS
Active power P, P1, P2, P3 total
Reactive power Q, Q1, Q2, Q3 total
Apparent power S, S1, S2, S3 total
Power factor
Active energy Ep IN/OUT/tot
Reactive energy Eq IN/OUT/tot
Apparent energy Es IN/OUT/tot
Demand current I1, I2, I3, In, Iavg
Demand power P, Q, S
Frequency
Phase sequence
Earth leakage current
Total current harmonic distortion THD (I)
Total voltage harmonic distortion THD (V)
Unbalance current
Unbalance voltage
Measurement voltage208…828 V AC 50/60 Hz phase to phase
120…480 V AC 50/60 Hz phase to neutral
Frequency measurement range40…70 Hz
Measurement accuracyCurrent I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40…1600 x 1.2 A
Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40…4000 x 1.2 A
Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80…6300 x 1.2 A
Neutral current IN: +/- 1 %
Ground fault current Ig: +/- 5 %
Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208…690 x 1.2 V
Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120…400 x 1.2 V
Active power P, P1, P2, P3, Pdemand: +/- 1 %
Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 %
Apparent power S, S1, S2, S3, Sdemand: +/- 1 %
Power factor: +/- 2 %
Active energy Ep IN/OUT/tot: +/- 1 %
Reactive energy Ep IN/OUT/tot: +/- 2 %
Apparent energy Es IN/OUT/tot: +/- 1 %
Frequency: +/- 0.005 Hz
Earth leakage current: +/- 10 %
Unbalance current: +/- 0.5 %
Accuracy classClass 5: total current harmonic distortion THD (I)
Class 0.5: unbalance voltage
Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h)
Class 2: total voltage harmonic distortion THD (V)
Display typeLCD display – 128 x 96 pixels
Communication port protocolBluetooth 4.0 LE peer to peer 30 kbit/s
NFC peer to peer 28800 bauds conforming to ISO 15963
USB peer to peer 115 kbauds
Data recordingTime stamping
Data logs
Event logs
Maintenance logs
Min/max of instantaneous values
Alarm logs
Environment
StandardsEN/IEC 60947-1
EN/IEC 60092-202
EN/IEC 60947-2
EN/IEC 60255-1
EN/IEC 61010-1
Mounting locationIndoor use only
Environmental characteristicWet location not approved for use conforming to IEC 61010-1
Electromagnetic compatibilityElectrostatic discharge immunity test conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Conducted and radiated emissions A conforming to CISPR 22
Overvoltage categoryIV conforming to IEC 61010-1
Measurement categoryCategory IV conforming to IEC 61010-2-30
Pollution degree3 conforming to IEC 60947-1
Ambient air temperature for operation-25…70 °C (operating)
-35 °C (for start-up of product)
Relative humidity95 % at 55 °C conforming to IEC 60068-2-30
Operating altitude<= 2000 m without derating
<= 4000 m with operational voltage derating 600 V AC
<= 5000 m with operational voltage derating 560 V AC
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.8 cm
Package 1 Width8.0 cm
Package 1 Length21.5 cm
Package 1 Weight318.0 g
Contractual warranty
Warranty18 months

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews

Reviews about the product Schneider LV865307