Schneider NJGF36250TW

0.00

The price is not final. Please check with the manager!

Schneider Electric PowerPacT multistandard – J-Frame – 250 A – 65 KA – Therm-Mag trip unit

Ask a Question

Datasheet

Main
Range of productPowerPact multistandard
RangePowerPact
Product nameJ-Frame
Device short nameJ-Frame
Product or component typeCircuit breaker
Device applicationDistribution
Complementary
Poles description3P
Control typeToggle
Mounting modeUnit mount
Mounting supportBackplate
Flush
DIN rail
Electrical connectionTerminal nut line side
Terminal nut load side
[In] rated current250 A at 40 °C
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ue] rated operational voltage525 V AC 50/60 Hz conforming to IEC 60947-2
690 V AC 50/60 Hz conforming to IEC 947-2
600 V AC 50/60 Hz conforming to UL 489
Breaking capacity codeJG
Suitability for isolationYes
Utilisation categoryCategory A
Mechanical durability5000 cycles
Electrical durability1000 cycles
Connection pitch45 mm
Local signallingON/OFF indication
Contact position indicatorYes
Trip unit nameTM
Trip unit technologyThermal-magnetic
Trip unit protection functionsBasic protection
Trip unit rating250 A
Display type3 LEDs
Breaking capacityIcu: 65 kA at 220/240 V – AC conforming to IEC 947-2
Icu: 35 kA at 380/415 V – AC conforming to IEC 947-2
Icu: 35 kA at 440/480 V – AC conforming to IEC 947-2
Icu: 18 kA at 500/525 V – AC conforming to IEC 947-2
65 kA at 240 V – AC conforming to UL 489
35 kA at 480 V – AC conforming to UL 489
18 kA at 600 V – AC conforming to UL 489
[Ics] rated service breaking capacityIcs: 65 kA at 220/240 V – AC conforming to IEC 947-2
Ics: 35 kA at 380/415 V – AC conforming to IEC 947-2
Ics: 35 kA at 440/480 V – AC conforming to IEC 947-2
Ics: 18 kA at 500/525 V – AC conforming to IEC 947-2
Long time pick-up adjustment type IrFixed
long time pick-up adjustment range1 In
Short-time pick-up adjustment type IsdAdjustable
[Isd] short-time pick-up adjustment range5…10 x In
Overvoltage categoryII
Provision for padlockingNon padlockable
Height191 mm
Width104 mm
Depth86 mm
StandardsNMX J-266
UL 489
W-C-375B/GEN
CSA C22.2 No 5
IEC 60947-2
NEMA AB1
Product certificationsCE
CCC
Net weight2.4 kg
Tightening torque25 N.m for 95…185 mm² (AWG 3/0…350 kcmil)
Environment
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60947-1
3 conforming to IEC 60664-1
Ambient air temperature for operation40 °C
Ambient air temperature for storage-50…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height13.018 cm
Package 1 Width18.415 cm
Package 1 Length21.433 cm
Package 1 Weight2.243 kg
Unit Type of Package 2S04
Number of Units in Package 26
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight14.224 kg

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews

Reviews about the product Schneider NJGF36250TW