Schneider NJGF36250TW

0.00

The price is not final. Please check with the manager!

Schneider Electric PowerPacT multistandard – J-Frame – 250 A – 65 KA – Therm-Mag trip unit

Contact Sales

Datasheet

Main
Range of product PowerPact multistandard
Range PowerPact
Product name J-Frame
Device short name J-Frame
Product or component type Circuit breaker
Device application Distribution
Complementary
Poles description 3P
Control type Toggle
Mounting mode Unit mount
Mounting support Backplate
Flush
DIN rail
Electrical connection Terminal nut line side
Terminal nut load side
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 525 V AC 50/60 Hz conforming to IEC 60947-2
690 V AC 50/60 Hz conforming to IEC 947-2
600 V AC 50/60 Hz conforming to UL 489
Breaking capacity code JG
Suitability for isolation Yes
Utilisation category Category A
Mechanical durability 5000 cycles
Electrical durability 1000 cycles
Connection pitch 45 mm
Local signalling ON/OFF indication
Contact position indicator Yes
Trip unit name TM
Trip unit technology Thermal-magnetic
Trip unit protection functions Basic protection
Trip unit rating 250 A
Display type 3 LEDs
Breaking capacity Icu: 65 kA at 220/240 V – AC conforming to IEC 947-2
Icu: 35 kA at 380/415 V – AC conforming to IEC 947-2
Icu: 35 kA at 440/480 V – AC conforming to IEC 947-2
Icu: 18 kA at 500/525 V – AC conforming to IEC 947-2
65 kA at 240 V – AC conforming to UL 489
35 kA at 480 V – AC conforming to UL 489
18 kA at 600 V – AC conforming to UL 489
[Ics] rated service breaking capacity Ics: 65 kA at 220/240 V – AC conforming to IEC 947-2
Ics: 35 kA at 380/415 V – AC conforming to IEC 947-2
Ics: 35 kA at 440/480 V – AC conforming to IEC 947-2
Ics: 18 kA at 500/525 V – AC conforming to IEC 947-2
Long time pick-up adjustment type Ir Fixed
long time pick-up adjustment range 1 In
Short-time pick-up adjustment type Isd Adjustable
[Isd] short-time pick-up adjustment range 5…10 x In
Overvoltage category II
Provision for padlocking Non padlockable
Height 191 mm
Width 104 mm
Depth 86 mm
Standards NMX J-266
UL 489
W-C-375B/GEN
CSA C22.2 No 5
IEC 60947-2
NEMA AB1
Product certifications CE
CCC
Net weight 2.4 kg
Tightening torque 25 N.m for 95…185 mm² (AWG 3/0…350 kcmil)
Environment
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Pollution degree 3 conforming to IEC 60947-1
3 conforming to IEC 60664-1
Ambient air temperature for operation 40 °C
Ambient air temperature for storage -50…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 13.018 cm
Package 1 Width 18.415 cm
Package 1 Length 21.433 cm
Package 1 Weight 2.243 kg
Unit Type of Package 2 S04
Number of Units in Package 2 6
Package 2 Height 30.0 cm
Package 2 Width 40.0 cm
Package 2 Length 60.0 cm
Package 2 Weight 14.224 kg