Datasheet
| Range | TeSys |
|---|---|
| Range of product | TeSys F |
| Product or component type | Contactor |
| Device short name | LC1F |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
| [Uc] control circuit voltage | 230 V AC 40…400 Hz |
| [Ie] rated operational current | 1000 A (at <40 °C) at <= 440 V AC AC-1 |
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|---|
| [Ith] conventional free air thermal current | 1000 A (at 40 °C) 1250 A |
| Rated breaking capacity | 5040 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 5050 A 40 °C – 10 s 4400 A 40 °C – 30 s 3400 A 40 °C – 1 min 2200 A 40 °C – 3 min 1600 A 40 °C – 10 min |
| Associated fuse rating | 1000 A gG at <= 440 V 630 A aM at <= 440 V |
| Average impedance | 0.12 mOhm – Ith 1000 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| Power dissipation per pole | 120 W AC-1 |
| Overvoltage category | III |
| power pole contact composition | 4 NO |
| Control circuit voltage limits | Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C) Drop-out: 0.25…0.5 Uc 40…400 Hz (at 55 °C) |
| Mechanical durability | 5 Mcycles |
| Inrush power in VA | 1650 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
| Hold-in power consumption in VA | 22 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
| Maximum operating rate | 1200 cyc/h 55 °C |
| Operating time | 40…80 ms closing 100…200 ms opening |
| Connections – terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) – busbar cross section: 60 x 5 mm Power circuit: bolted connection |
| Tightening torque | Control circuit: 1.2 N.m Power circuit: 58 N.m |
| Mounting support | Plate |
| Heat dissipation | 20 W |
| Standards | EN 60947-1 IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1 |
| Product certifications | CCC ABS UL LROS (Lloyds register of shipping) DNV CB RMRoS RINA BV UKCA |
| Compatibility code | LC1F |
| Control circuit type | AC at 40…400 Hz |
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
|---|---|
| Protective treatment | TH |
| Ambient air temperature for operation | -5…55 °C |
| Ambient air temperature for storage | -60…80 °C |
| Permissible ambient air temperature around the device | -40…70 °C |
| Height | 304 mm |
| Width | 389 mm |
| Depth | 255 mm |
| Operating altitude | 3000 m without derating |
| Net weight | 21.5 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 29.0 cm |
| Package 1 Width | 34.0 cm |
| Package 1 Length | 43.0 cm |
| Package 1 Weight | 21.6 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 77.0 cm |
| Package 2 Width | 80.0 cm |
| Package 2 Length | 60.0 cm |
| Package 2 Weight | 94.9 kg |
| Warranty | 18 months |
|---|