Schneider Electric TeSys GV7 – circuit breaker – 3P – AC-3 – 48…80 A – thermal-magnetic

Contact Sales

Datasheet

Main
Range TeSys
Product name TeSys GV7
Product or component type Circuit breaker
Device short name GV7R
Device application Motor
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range 48…80 A
Trip unit technology Thermal-magnetic
Complementary
Mounting mode By screws
By clips
Mounting support Kit for fixing the switchgear
Rail
Panel mounting
Flush
Mounting position Vertical
Motor power kW 37 kW at 400…415 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
55 kW at 660…690 V AC 50/60 Hz
Control type Rocker lever
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 750 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 80 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
power dissipation per pole 5 W
Power dissipation per pole 5 W
Mechanical durability 50000 cycles
Electrical durability 30000 cycles for AC-3 at 440 V In
50000 cycles for AC-3 at 440 V In/2
Maximum operating rate 25 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connection pitch 35 mm without spreaders
45 mm with spreaders
Connections – terminals Bars
Cable with lug – external diameter: 10 mm
Screw
Bare cable connectors 1.5…95 mm²
Tightening torque 10 N.m on screw M6 screw type
15 N.m on bare cable connectors for cable 1.5…95 mm²
Mechanical robustness Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations: 2.5 Gn, 0…25 Hz conforming to IEC 60068-2-6
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
Height 161 mm
Width 105 mm
Depth 111 mm
Net weight 2.04 kg
Environment
Standards VDE 0660
NF C 63-650
EN/IEC 60947-4-1
NF C 63-120
NF C 79-130
VDE 0113
EN/IEC 60947-2
EN/IEC 60947-1
Product certifications DNV
UL
Protective treatment TC
IP degree of protection IP405 conforming to IEC 60529 (with terminal shrouds)
Pollution degree 3
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -55…95 °C
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 2000 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.5 cm
Package 1 Width 14 cm
Package 1 Length 17.5 cm
Package 1 Weight 1.934 kg
Contractual warranty
Warranty 18 months