Datasheet
Range | TeSys |
---|---|
Product name | TeSys GV7 |
Product or component type | Circuit breaker |
Device short name | GV7R |
Device application | Motor |
Poles description | 3P |
Network type | AC |
Utilisation category | AC-3 conforming to IEC 60947-4-1 |
Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
Breaking capacity | 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
thermal protection adjustment range | 48…80 A |
Trip unit technology | Thermal-magnetic |
Mounting mode | By screws By clips |
---|---|
Mounting support | Kit for fixing the switchgear Rail Panel mounting Flush |
Mounting position | Vertical |
Motor power kW | 37 kW at 400…415 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 55 kW at 660…690 V AC 50/60 Hz |
Control type | Rocker lever |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ith] conventional free air thermal current | 80 A conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
power dissipation per pole | 5 W |
Power dissipation per pole | 5 W |
Mechanical durability | 50000 cycles |
Electrical durability | 30000 cycles for AC-3 at 440 V In 50000 cycles for AC-3 at 440 V In/2 |
Maximum operating rate | 25 cyc/h |
Rated duty | Continuous conforming to IEC 60947-4-1 |
Connection pitch | 35 mm without spreaders 45 mm with spreaders |
Connections – terminals | Bars Cable with lug – external diameter: 10 mm Screw Bare cable connectors 1.5…95 mm² |
Tightening torque | 10 N.m on screw M6 screw type 15 N.m on bare cable connectors for cable 1.5…95 mm² |
Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations: 2.5 Gn, 0…25 Hz conforming to IEC 60068-2-6 |
Suitability for isolation | Yes conforming to IEC 60947-1 |
Phase failure sensitivity | Yes conforming to IEC 60947-4-1 § 7-2-1-5-2 |
Height | 161 mm |
Width | 105 mm |
Depth | 111 mm |
Net weight | 2.04 kg |
Standards | VDE 0660 NF C 63-650 EN/IEC 60947-4-1 NF C 63-120 NF C 79-130 VDE 0113 EN/IEC 60947-2 EN/IEC 60947-1 |
---|---|
Product certifications | DNV UL |
Protective treatment | TC |
IP degree of protection | IP405 conforming to IEC 60529 (with terminal shrouds) |
Pollution degree | 3 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -55…95 °C |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Operating altitude | 2000 m |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 11.5 cm |
Package 1 Width | 14 cm |
Package 1 Length | 17.5 cm |
Package 1 Weight | 1.934 kg |
Warranty | 18 months |
---|