Datasheet
Range | ComPact |
---|---|
Range of product | ComPact NSX400…630 |
Product or component type | Trip unit |
Trip unit name | MicroLogic 5.3 E |
Trip unit technology | Electronic |
Range compatibility | ComPact NSX400 ComPact NSX630 |
Device application | Distribution |
Number of poles | 4P |
Protected poles description | 3t + N/2 4t 3t + OSN 3t |
Neutral position | Left |
Trip unit protection functions | LSI |
Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
Trip unit rated current | 400 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
---|---|
[Ir] long-time protection pick-up adjustment range | 160…400 A |
Long-time protection delay adjustment type tr | Adjustable |
[tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |
Thermal memory | 20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range | 1.5…10 x Ir |
Short-time protection delay adjustment type tsd | Adjustable |
[tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Instantaneous protection pick-up adjustment type Ii | Adjustable |
[Ii] instantaneous protection pick-up adjustment range | 1.5…12 x In |
Earth-leakage protection | Without |
Neutral protection settings | 0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) No protection (3t) |
Zone selective interlocking ZSI | With |
Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
Display type | LCD display |
type of measurement | Energy meter |
Communication of data | Instantaneous and demand values Maintenance indicators Maximeters/minimeters Energy metering Demand current and power Protection and alarm settings Time-stamped histories and event tables Power quality |
Electrical data recording | Maintenance indicators |
Standards | EN/IEC 60947-2 UL 508 |
---|---|
Product certifications | Marine EAC CCC |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 13.8 cm |
Package 1 Width | 17.6 cm |
Package 1 Length | 21.6 cm |
Package 1 Weight | 1.834 kg |
Unit Type of Package 2 | S04 |
Number of Units in Package 2 | 10 |
Package 2 Height | 30.0 cm |
Package 2 Width | 40.0 cm |
Package 2 Length | 60.0 cm |
Package 2 Weight | 19.106 kg |
Warranty | 18 months |
---|