Range | ComPact |
---|---|
Range of product | ComPact NSX100…250 |
Product or component type | Trip unit |
Trip unit name | MicroLogic 7.2 E AL |
Trip unit technology | Electronic |
Range compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
Device application | Distribution |
Number of poles | 4P |
Protected poles description | 3t 3t + N/2 4t 3t + OSN |
Neutral position | Left |
Trip unit protection functions | LSI |
Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
Trip unit rated current | 100 A at 40 °C |
[Ue] rated operational voltage | 440 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
---|---|
[Ir] long-time protection pick-up adjustment range | 40…100 A |
Long-time protection delay adjustment type tr | Adjustable |
[tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |
Thermal memory | 20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd | Adjustable |
[Isd] Short-time protection pick-up adjustment range | 1.5…10 x Ir |
Short-time protection delay adjustment type tsd | Adjustable |
[tsd] Short-time protection delay adjustment range | 0…0.4 s |
Instantaneous protection pick-up adjustment type Ii | Adjustable |
[Ii] instantaneous protection pick-up adjustment range | 1500 A |
Earth-leakage protection | Integrated |
Earth-leakage protection class | Class A |
Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
[IΔn] earth-leakage protection sensitivity adjustment range | 30 mA 5 A 100 mA 300 mA 500 mA 3 A 1 A |
Earth-leakage protection specific mode | OFF using the IΔn rotary switch |
Earth-leakage protection time delay adjustement type Δt | Adjustable |
[Δt] Earth-leakage protection time delay adjustment range | 0 ms 150 ms 1 s 500 ms 60 ms |
Neutral protection settings | 0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) No protection (3t) |
Zone selective interlocking ZSI | Without |
Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
Display type | LCD display |
type of measurement | Energy meter |
Communication of data | Demand current and power Protection and alarm settings Earth leakage current Maximeters/minimeters Test reports Maintenance indicators Instantaneous and demand values Energy metering Time-stamped histories and event tables Power quality |
Standards | IEC 60947-2 EN 60947-2 UL 508 NEMA AB1 |
---|---|
Product certifications | EAC CCC CB |
Pollution degree | 3 conforming to IEC 60947-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 9.5 cm |
Package 1 Width | 11.0 cm |
Package 1 Length | 15.0 cm |
Package 1 Weight | 806.0 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 10 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 8.5 kg |