Datasheet
| Range | ComPact |
|---|---|
| Range of product | ComPact NSX100…250 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 7.2 E AL |
| Trip unit technology | Electronic |
| Range compatibility | ComPact NSX160 ComPact NSX250 |
| Device application | Distribution |
| Number of poles | 4P |
| Protected poles description | 3t + N/2 4t 3t 3t + OSN |
| Neutral position | Left |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 160 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 63…160 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5…10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 2400 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
| [IΔn] earth-leakage protection sensitivity adjustment range | 100 mA 3 A 30 mA 1 A 500 mA 5 A 300 mA |
| Earth-leakage protection specific mode | OFF using the IΔn rotary switch |
| Earth-leakage protection time delay adjustement type Δt | Adjustable |
| [Δt] Earth-leakage protection time delay adjustment range | 500 ms 60 ms 1 s 150 ms 0 ms |
| Neutral protection settings | 0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) No protection (3t) |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| type of measurement | Energy meter |
| Communication of data | Energy metering Maintenance indicators Time-stamped histories and event tables Protection and alarm settings Instantaneous and demand values Test reports Power quality Earth leakage current Maximeters/minimeters Demand current and power |
| Standards | UL 508 IEC 60947-2 NEMA AB1 EN 60947-2 |
|---|---|
| Product certifications | CCC EAC CB |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.000 cm |
| Package 1 Width | 11.100 cm |
| Package 1 Length | 15.000 cm |
| Package 1 Weight | 810.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.444 kg |
| Warranty | 18 months |
|---|