Schneider ATV61QC40Y

0.00

The price is not final. Please check with the manager!

Schneider Electric variable speed drive ATV61Q – 400kW / 450HP – 500…690V – IP20

Contact Sales

Datasheet

Main
Range of product Altivar 61Q
Product or component type Variable speed drive
Device short name ATV61Q
Product destination Asynchronous motors
Synchronous motors
Product specific application Pumping and ventilation machine
Assembly style With heat sink
EMC filter Integrated
Network number of phases 3 phases
[Us] rated supply voltage 500…690 V – 15…10 %
Supply voltage limits 425…759 V
Supply frequency 50…60 Hz – 5…5 %
Network frequency limits 47.5…63 Hz
Motor power kW 315 kW, 3 phases at 500 V
400 kW, 3 phases at 690 V
Motor power hp 450 hp, 3 phases at 575 V
Maximum motor cable length 15 m shielded cable without motor choke
30 m unshielded cable without motor choke
250 m shielded cable with motor choke
400 m unshielded cable with motor choke
Line current 390 A for 600 V 3 phases 315 kW / 450 hp
394 A for 690 V 3 phases 315 kW / 450 hp
426 A for 500 V 3 phases 315 kW / 450 hp
Complementary
Prospective line Isc 35 kA for 3 phases
Continuous output current 420 A at 2.5 kHz, 575 V – 3 phases
420 A at 2.5 kHz, 690 V – 3 phases
462 A at 2.5 kHz, 500 V – 3 phases
Maximum transient current 554.4 A for 60 s, 3 phases
Speed drive output frequency 0.1…500 Hz
Nominal switching frequency 2.5 kHz
Switching frequency 2…4.9 kHz adjustable
2.5…4.9 kHz with derating factor
Speed range 1…100 in open-loop mode, without speed feedback
Speed accuracy +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn
Torque accuracy +/- 15 % in open-loop mode, without speed feedback
Transient overtorque 130 % of nominal motor torque +/- 10 % for 60 s
Braking torque <= 125 % with braking resistor
30 % without braking resistor
Asynchronous motor control profile Voltage/frequency ratio, 5 points
Voltage/frequency ratio – Energy Saving, quadratic U/f
Voltage/frequency ratio, 2 points
Flux vector control without sensor, standard
Synchronous motor control profile Vector control without sensor, standard
Regulation loop Frequency PI regulator
Motor slip compensation Can be suppressed
Not available in voltage/frequency ratio (2 or 5 points)
Adjustable
Automatic whatever the load
Local signalling 1 LED (red) for drive voltage
Output voltage <= power supply voltage
Isolation Between power and control terminals
Type of cable With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Electrical connection Terminal 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR)
Terminal 4 x 185 mm² / 3 x 350 kcmil (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
Terminal 4 x 185 mm² / 3 x 350 kcmil (PC/-, PA/+)
Tightening torque 41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
41 N.m, 360 lb.in (PC/-, PA/+)
0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR)
Supply External supply: 24 V DC (19…30 V) – 30 W
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 %, <10 mA with overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 mA with overload and short-circuit protection
Analogue input number 2
Analogue input type AI2 software-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign
AI2 software-configurable current: 0…20 mA, impedance: 242 Ohm, resolution 11 bits
Sampling duration 2 ms +/- 0.5 ms (LI6)if configured as logic input – discrete input
2 ms +/- 0.5 ms (AI1-/Al1+) – analog input
2 ms +/- 0.5 ms (Al2) – analog input
2 ms +/- 0.5 ms (AO1) – analog output
2 ms +/- 0.5 ms (LI1…LI5) – discrete input
Accuracy +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
+/- 0.6 % (AI2) for a temperature variation 60 °C
+/- 1 % (AO1) for a temperature variation 60 °C
Linearity error +/- 0.15 % of maximum value (AI1-/Al1+)
+/- 0.15 % of maximum value (AI2)
+/- 0.2 % (AO1)
Analogue output number 1
Analogue output type AO1 software-configurable current: 0…20 mA, impedance: 500 Ohm, resolution 10 bits
AO1 software-configurable voltage: 0…10 V DC, impedance: 470 Ohm, resolution 10 bits
AO1 software-configurable logic output 10 V 20 mA
Discrete output number 2
Discrete output type Configurable relay logic: (R1A, R1B, R1C) NO/NC – 100000 cycles
Configurable relay logic: (R2A, R2B) NO – 100000 cycles
Response time R1A, R1B, R1C <= 7 ms, tolerance +/- 0.5 ms
R2A, R2B <= 7 ms, tolerance +/- 0.5 ms
<= 100 ms in STO (Safe Torque Off)
Minimum switching current 3 mA at 24 V DC for configurable relay logic
Maximum switching current 2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (R1, R2)
2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (R1, R2)
5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (R1, R2)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (R1, R2)
Discrete input number 7
Discrete input type LI1…LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
LI6: switch-configurable PTC probe 0…6, impedance: 1500 Ohm
PWR: safety input 24 V DC, impedance: 1500 Ohm
Discrete input logic Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (LI1…LI5), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (LI1…LI5), < 5 V (state 0), > 11 V (state 1)
Acceleration and deceleration ramps Automatic adaptation of ramp if braking capacity exceeded, by using resistor
S, U or customized
Linear adjustable separately from 0.01 to 9000 s
Braking to standstill By DC injection
Protection type Against exceeding limit speed: drive
Against input phase loss: drive
Break on the control circuit: drive
Input phase breaks: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Overvoltages on the DC bus: drive
Power removal: drive
Short-circuit between motor phases: drive
Thermal protection: drive
Motor phase break: motor
Power removal: motor
Thermal protection: motor
Dielectric strength 3110 V DC between earth and power terminals
5345 V DC between control and power terminals
Insulation resistance > 1 mOhm 500 V DC for 1 minute to earth
Frequency resolution Analog input: 0.024/50 Hz
Display unit: 0.1 Hz
communication port protocol Modbus
CANopen
Connector type 1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen
Physical interface 2-wire RS 485 for Modbus
Transmission frame RTU for Modbus
Transmission rate 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
Data format 8 bits, 1 stop, even parity for Modbus on front face
8 bits, odd even or no configurable parity for Modbus on terminal
Type of polarization No impedance for Modbus
Number of addresses 1…127 for CANopen
1…247 for Modbus
Method of access Slave CANopen
Type of cooling Water cooled
Cooling fluid type Water-glycol mixture
Industrial water
Clean water
operating temperature water 5…55 °C
Thermal losses 6000 W 100 % of line current for area of liquid cooling (power part)
1020 W 100 % of line current for area of air cooling (control part)
Flow velocity range 24
Pressure drop 1 bar
volume of cooling water 0.4 l
Operating position Vertical +/- 10 degree
Net weight 140 kg
Option card Communication card for APOGEE FLN
Communication card for BACnet
Communication card for CC-Link
Communication card for DeviceNet
Communication card for EtherNet/IP
Communication card for Fipio
Communication card for Interbus-S
Communication card for LonWorks
Communication card for METASYS N2
Communication card for Modbus Plus
Communication card for Modbus TCP
Communication card for Modbus/Uni-Telway
Communication card for Profibus DP
Communication card for Profibus DP V1
Controller inside programmable card
I/O extension card
Multi-pump card
Width 585 mm
Height 950 mm
Depth 377 mm
Environment
Ambient air temperature for operation -10…50 °C (without derating)
50…60 °C (with derating factor)
Ambient air temperature for storage -25…70 °C
Operating altitude <= 1000 m without derating
1000…2260 m with current derating 1 % per 100 m
Electromagnetic compatibility Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Pollution degree 3 conforming to EN/IEC 61800-5-1
3 conforming to UL 840
IP degree of protection IP00 conforming to EN/IEC 60529
IP00 conforming to EN/IEC 61800-5-1
IP30 on side parts conforming to EN/IEC 60529
IP30 on side parts conforming to EN/IEC 61800-5-1
IP30 on the front panel conforming to EN/IEC 60529
IP30 on the front panel conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP54 on lower part conforming to EN/IEC 61800-5-1
Vibration resistance 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…10 Hz) conforming to EN/IEC 60068-2-6
Shock resistance 4 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
Noise level 77 dB conforming to 86/188/EEC
Standards EN/IEC 61800-3
EN 61800-3 environments 1 category C3
EN 55011 class A group 2
EN 61800-3 environments 2 category C3
IEC 60721-3-3 class 3C2
UL Type 1
EN/IEC 61800-5-1
Product certifications DNV
NOM 117
C-Tick
CSA
GOST
UL
Marking CE
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 53.0 cm
Package 1 Width 63.5 cm
Package 1 Length 129.0 cm
Package 1 Weight 160.0 kg
Contractual warranty
Warranty 18 months

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews

Reviews about the product Schneider ATV61QC40Y