Home
» Sick » Sick PAC50-CGA

Sick PAC50-CGA

129.11

The price is not final. Please check with the manager!
SKU: PAC50-CGA Categories: , , Brand:
  • Electronic pressure switch for pneumatic applications
  • Large display shows system pressure, output states and set switching points
  • Three large function keys and intuitive menu navigation
Contact Sales
Delivery time 3–10 business days. Express available.
Returns 14 days return. New condition only.
Shipping EU, USA, worldwide.
DHL, DPD, UPS.

Datasheet

Specification:

Part Number 1062970
CRUus certificate: +
Ambient temperature: 0 °C … +60 °C
Accuracy: ≤ ± 1.5 % of span (Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement according to IEC 61298-2)), ≤ ± 2 % of span incl. temperature error (Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement according to IEC 61298-2))
Storage temperature: -20 °C … +80 °C
Display: Update: 1,000, 500, 200, 100 ms (adjustable), Pressure display: 4 digits, 16 segments, Pressure unit in display can be switched: bar, MPa, kPa, psi and inHg, LCD with LED backlight (green/red), can be rotated electronically by 180°
Measuring range: 0 bar … 6 bar
Weight sensor: Ca. 40 g
Diagnostics output: Switching output 2 can be set as diagnostics output
Enclosure rating: IP 65 / IP 67 According to IEC 60529
Setting accuracy of switching outputs: ≤ ± 0.2 % of span
Output signal: 2 x PNP/NPN/Push-Pull
Housing material: Seals: NBR, Housing: polycarbonate, DIN rail mounting: POM, Buttons: TPE
Process connection: 2 x G ?
Non-linearity: ≤ ± 0.5 % (of span (Best Fit Straight Line, BFSL) according to IEC 61298-2)
Process temperature: 0 °C … +60 °C
Pressure type: Gauge pressure
Medium: Dry compressed air
Non-repeatability: ≤ ± 0.2 % of span
Initialization time: 300 ms
Zero point adjustment: Max. + 5 % of span
Gauge pressure: -1 bar … 0 bar; -1 bar … +1 bar; 0 bar … +6 bar; 0 bar … +10 bar
Vibration load: Max. 5 g (10 … 150 Hz), xyz, according to DIN EN 60068-2-6
Relative humidity: ≤ 90 %
CE-conformity: EMC directive: 2004/108/EC, EN 61326-2-3
Analog signal output and ohmic load RA: Load resistance for voltage output > 3 kOhm, Load resistance for current output < 600 Ohm, Optional, 4 mA ... 20 mA / 0 V… 10 V. Automatic detection depending on connected load or programmable. Output signals can be inverted: 20 mA … 4 mA / 10 V … 0 V
Rated temperature range: +10 °C … +60 °C
Electrical safety: Short-circuit protection: QA, Q1, Q2 towards M and L+, Protection class: III, Overvoltage protection: 32 V DC, Reverse polarity protection: L+ towards M
RoHS certificate: +
CULus certificate:
Shock load: Max. 30 g, xyz according to IEC 60068-2-27 (11 ms, mechanical shock)
Power consumption: Max. 40 mA at L+ = 24 VDC
Protection class III: +