Home
» IFM Electronic » IFM PN2515 Pressure sensor with display

IFM PN2515 Pressure sensor with display

391.33

The price is not final. Please check with the manager!
SKU: PN2515 Categories: , , Brand:

PN-006-REG14-MFRKG/US/ /V

  • Two switching outputs, one of them programmable as IO-Link and one as analogue output
  • Red/green display for clear identification of the acceptable range
  • The process
Contact Sales
Delivery time 3–10 business days. Express available.
Returns 14 days return. New condition only.
Shipping EU, USA, worldwide.
DHL, DPD, UPS.

Datasheet

Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
-1…6 bar -14.5…87 psi -100…600 kPa
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature [°C] -25…80
Min. bursting pressure
100 bar 1500 psi 10000 kPa
Pressure rating
40 bar 600 psi 4000 kPa
Vacuum resistance [mbar] -1000
Type of pressure relative pressure; vacuum
Electrical data
Operating voltage [V] 18…30 DC; (to SELV/PELV)
Current consumption [mA] < 35
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 250
Switching frequency DC [Hz] < 500
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable 1:5)
Max. load [Ω] 500
Analogue voltage output [V] 0…10; (scalable 1:5)
Min. load resistance [Ω] 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1…6 bar -14.5…87 psi -100…600 kPa
Set point SP
-0.95…6 bar -13.8…87 psi -95…600 kPa
Reset point rP
-0.98…5.97 bar -14.2…86.6 psi -98…597 kPa
Analogue start point
-1…4.8 bar -14.5…69.6 psi -100…480 kPa
Analogue end point
0.2…6 bar 2.9…87 psi 20…600 kPa
Min. difference between SP and rP
0.03 bar 0.5 psi 3 kPa
In steps of
0.001 bar 0.1 psi 1 kPa
Accuracy / deviations
Switch point accuracy [% of the span] < ± 0,4; (Turn down 1:1)
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span] < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span] < ± 0,1; (Turn down 1:1)
Long-term stability [% of the span] < ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,2; (-0...80 °C)
Temperature coefficient span [% of the span / 10 K] < ± 0,2; (-0...80 °C)
Notes on the accuracy / deviation switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Response times
Response time [ms] < 1.5
Delay time programmable dS, dr [s] 0…50
Damping process value dAP [s] 0…4
Damping for the analogue output dAA [s] 0…4
Max. response time analogue output [ms] 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
SIO mode yes
Required master port type A; (when pin 2 not connected: B)
Min. process cycle time [ms] 3
IO-Link resolution pressure [bar] 0.005
IO-Link process data (cyclical)
function bit length
pressure 16
device status 4
binary switching information 2
IO-Link functions (acyclical) application specific tag
Supported DeviceIDs
Type of operation DeviceID
Default 1203
Note
For further information please see the IODD PDF file under “Downloads”
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -40…100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 20 g (10…2000 Hz)
MTTF [years] 167
UL approval
UL Approval no. J012
File number UL E174189
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 272.5
Materials stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM
Min. pressure cycles 100 million
Tightening torque [Nm] 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5
Process connection sealing FKM (DIN EN ISO 1179-2)
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit 3 x LED, green (bar, psi, MPa)
switching status 2 x LED, yellow
measured values alphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews