Datasheet
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | |||
|---|---|---|---|---|
| Measuring range |
|
|||
| Process connection | homogeniser connection |
Application
| Special feature | Gold-plated contacts | |||
|---|---|---|---|---|
| Measuring element | diaphragm seal | |||
| Application | flush mountable for the food and beverage industry | |||
| Media | liquids and gases | |||
| Medium temperature [°C] | 5…90; (for further details see section Diagrams and graphs) | |||
| Min. bursting pressure |
|
|||
| Pressure rating |
|
|||
| Vacuum resistance [mbar] | -1000 | |||
| Type of pressure | relative pressure |
Electrical data
| Operating voltage [V] | 18…30 DC; (to SELV/PELV) |
|---|---|
| Current consumption [mA] | < 35 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 0.3 |
| Integrated watchdog | yes |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
|---|
Outputs
| Total number of outputs | 2 |
|---|---|
| Output signal | switching signal; analogue signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | < 500 |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4…20; (scalable 1:5) |
| Max. load [Ω] | 500 |
| Analogue voltage output [V] | 0…10; (scalable 1:5) |
| Min. load resistance [Ω] | 2000 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range |
|
|||
|---|---|---|---|---|
| Set point SP |
|
|||
| Reset point rP |
|
|||
| Analogue start point |
|
|||
| Analogue end point |
|
|||
| In steps of |
|
Accuracy / deviations
| Switch point accuracy [% of the span] | < ± 0,4; (Turn down 1:1) |
|---|---|
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span] | < ± 1; (linearity, incl. hysteresis and repeatability; limit value setting to DIN EN IEC 62828-1) |
| Hysteresis deviation [% of the span] | < ± 0,1; (Turn down 1:1) |
| Long-term stability [% of the span] | < ± 0,05; (Turn down 1:1; per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] | 0,2; (5…80 °C) |
| Temperature coefficient span [% of the span / 10 K] | 0,2; (5…80 °C) |
Response times
| Response time [ms] | < 1.5 |
|---|---|
| Delay time programmable dS, dr [s] | 0…50 |
| Damping process value dAP [s] | 0…4 |
| Damping for the analogue output dAA [s] | 0…4 |
| Max. response time analogue output [ms] | 3 |
Software / programming
| Parameter setting options | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
|---|
Interfaces
| Communication interface | IO-Link | ||||
|---|---|---|---|---|---|
| Transmission type | COM2 (38,4 kBaud) | ||||
| IO-Link revision | 1.1 | ||||
| SDCI standard | IEC 61131-9 | ||||
| Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | ||||
| SIO mode | yes | ||||
| Required master port type | A | ||||
| Process data analogue | 1 | ||||
| Process data binary | 2 | ||||
| Min. process cycle time [ms] | 2.3 | ||||
| Supported DeviceIDs |
|
Operating conditions
| Ambient temperature [°C] | 5…80 |
|---|---|
| Storage temperature [°C] | -40…100 |
| Protection | IP 67 |
Tests / approvals
| EMC |
|
||||
|---|---|---|---|---|---|
| Shock resistance |
|
||||
| Vibration resistance |
|
Mechanical data
| Weight [g] | 1479 |
|---|---|
| Materials | 1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); stainless steel (1.4435 / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials (wetted parts) | stainless steel (1.4435 / 316L) |
| Min. pressure cycles | 60 million; (at 1.2 times nominal pressure) |
| Process connection | homogeniser connection |
Displays / operating elements
| Display |
|
|---|
Remarks
| Pack quantity | 1 pcs. |
|---|
Electrical connection
| Connector: 1 x M12; coding: A; Contacts: gold-plated |