Datasheet
Range | TeSys |
---|---|
Product name | TeSys B |
Product or component type | Contactor |
Device short name | LC1BP |
Contactor application | Motor-heating-lighting |
Utilisation category | AC-4 AC-1 AC-3 |
Control circuit type | AC |
Coil type | Standard |
Poles description | 3P |
Pole contact composition | 3 NO |
[Ie] rated operational current | 2000 A (at <40 °C) AC AC-1 for power circuit 1500 A (at <55 °C) AC AC-3 for power circuit |
Motor power kW | 425 kW at 220…230 V AC 50/60 Hz (AC-3) 670 kW at 1000 V AC 50/60 Hz (AC-3) 700 kW at 500 V AC 50/60 Hz (AC-3) 750 kW at 380…400 V AC 50/60 Hz (AC-3) 750 kW at 660…690 V AC 50/60 Hz (AC-3) 800 kW at 415 V AC 50/60 Hz (AC-3) 800 kW at 440 V AC 50/60 Hz (AC-3) 220 kW at 400 V AC 50/60 Hz (AC-4) |
Auxiliary contact composition | 2 NO + 2 NC |
[Uc] control circuit voltage | 220 V AC 50…400 Hz |
Control circuit voltage limits | Operational: 0.85…1.1 Uc at 50…400 Hz Drop-out: 0.35…0.5 Uc at 50…400 Hz |
---|---|
[Ui] rated insulation voltage | 1000 V – for power circuit conforming to IEC 60158-1 1000 V – for power circuit conforming to IEC 60947-4 1500 V – for power circuit conforming to VDE 0110 group C |
Mounting mode | Fixed |
Mounting support | Notched mounting rails Bar support bracket |
Connections – terminals | Power circuit: bars 3 x – busbar cross section: 100 x 5 mm |
Tightening torque | Power circuit: 35 N.m – on bars |
[Ue] rated operational voltage | Power circuit: <= 1000 V AC 50/60 Hz |
[Ith] conventional free air thermal current | 2000 A (at 40 °C) for power circuit |
Irms rated making capacity | 15000 A at 1000 V AC for power circuit conforming to IEC 60158-1 15000 A at 1000 V AC for power circuit conforming to IEC 60947-4 |
Rated breaking capacity | 12000 A at 500 V for power circuit conforming to IEC 60158-1 12000 A at 500 V for power circuit conforming to IEC 60947-4 15000 A at 440 V for power circuit conforming to IEC 60158-1 15000 A at 440 V for power circuit conforming to IEC 60947-4 5000 A at 1000 V for power circuit conforming to IEC 60158-1 5000 A at 1000 V for power circuit conforming to IEC 60947-4 9000 A at 660…690 V for power circuit conforming to IEC 60158-1 9000 A at 660…690 V for power circuit conforming to IEC 60947-4 |
Associated fuse rating | 1600 A aM at <= 440 V for power circuit 2000 A gI at <= 440 V for power circuit |
Average impedance | 0.13 mOhm – Ith 2000 A 50 Hz for power circuit |
Power dissipation per pole | 290 W AC-3 – Ith 2000 A 520 W AC-1 – Ith 2000 A |
Inrush power in VA | 1300 VA |
Hold-in power consumption in VA | 31 VA 50/60 Hz |
Operating time | 100…150 ms closing 50…100 ms opening |
Mechanical durability | 1200000 cycles |
Maximum operating rate | 120 cyc/h 55 °C |
Height | 490 mm |
Width | 790 mm |
Depth | 475 mm |
Net weight | 94 kg |
Standards | NF C 63-110 BS 5424 VDE 0660 IEC 60158-1 IEC 60947-4 |
---|---|
Product certifications | RINA CSA BV |
Protective treatment | TC TH |
Ambient air temperature for operation | -5…55 °C |
Ambient air temperature for storage | -60…80 °C |
Operating altitude | 3000 m without derating |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 60 cm |
Package 1 Width | 90 cm |
Package 1 Length | 53 cm |
Package 1 Weight | 72 kg |
Warranty | 18 months |
---|