Schneider Electric Circuit breaker, EasyPact MVS, 3 Poles, 2000A, 65kA, MF, ET2, fixed, manual

Contact Sales

Datasheet

Main
Range EasyPact
Product name MVS20H
Device short name MVS20H
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
[In] rated current 2000 A at 40 °C
Network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code H
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET2I
Trip unit technology Electronic
Trip unit rating 2000 A
Complementary
Network frequency 50/60 Hz
Control type Manually operated
Mounting mode Fixed
Mounting support Rail
Base plate
Connection position Horizontal
Vertical
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Circuit breaker CT rating 2000 A
Breaking capacity 65 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 65 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making capacity 143 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 65 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
Protection type Instantaneous short-circuit protection
Overload protection (long time)
Fault indication Short-circuit
Overload
Internal fault
Long time pick-up adjustment type Ir Adjustable 9 settings
long time pick-up adjustment range 0.4…1 x In
long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Thermal memory 20 minutes before and after tripping
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range 1.5…10 x Ir
Zone selective interlocking ZSI With
current sensor rating range 400/2000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 352 mm
Width 422 mm
Depth 297 mm
Net weight 40 kg
Environment
Standards IEC 60947-2
Product certifications GOST
IEC
CCC
CCS
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
Ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 42.0 cm
Package 1 Width 35.0 cm
Package 1 Length 50.0 cm
Package 1 Weight 45.667 kg
Contractual warranty
Warranty 18 months