Datasheet
Range | ClimaSys |
---|---|
Product name | CU |
Product or component type | Cooling unit |
mounting type | Roof of enclosure |
Type of installation | Indoor |
Product destination | For enclosure |
Mounting mode | By screws |
Input voltage | 230 V 50/60 Hz |
Network number of phases | 1 phase |
Cooling power | 2800 Btu/h 50/60 Hz L35-L35 2320 Btu/h 50/60 Hz L35-L50 |
Height | 340 mm |
---|---|
Width | 600 mm |
Depth | 340 mm |
[In] rated current | 2.9 A |
Inrush current | 12 A |
Power consumption in W | 510 W at 50/60 Hz, L35-L35 560 W at 50/60 Hz, L35-L50 |
Energy efficiency ratio | 1.6 |
Control type | Electronic controller |
Temperature setting range | 20…50 °C |
Ambient air temperature for operation | 50 °C maximum: 20…46 °C inside the enclosure: 20…50 °C outside the enclosure: |
Noise level | 65 dB |
Pressure | 25 bar |
Flow rate | Internal circuit: 570 m3/h at 50/60 Hz External circuit: 860 m3/h at 50/60 Hz |
Net weight | 23 kg |
Cooling gas type | R134a (0.31 kg) |
Type of filter | Optional external circuit filter |
Protection type | Thermal protection: T 6 A Short-circuit protection (magnetic): |
Material | Steel |
Colour | Grey (RAL 7035) |
Product certifications | UL |
---|---|
Standards | DIN 3168 |
IP degree of protection | IP34 conforming to IEC 60529 (on the external circuit) IP54 conforming to IEC 60529 (on the internal circuit) |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 43.18 cm |
Package 1 Width | 40.64 cm |
Package 1 Length | 66.04 cm |
Package 1 Weight | 20.602 kg |
Unit Type of Package 2 | P12 |
Number of Units in Package 2 | 6 |
Package 2 Height | 143.5 cm |
Package 2 Width | 80 cm |
Package 2 Length | 120 cm |
Package 2 Weight | 252.6 kg |