Datasheet
| Product or component type | Basic frame |
| Device short name | Compact NSX100S |
| Circuit breaker name | Compact NSX100S |
| Poles description | 4P |
| Network type | DC |
| [In] rated current | 100 A ( 40 В°C ) |
| [Ui] rated insulation voltage | 800 V DC conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 750 V DC conforming to IEC 60947-2 |
| Breaking capacity code | S |
| Breaking capacity | Icu at 750 V DC 3P conforming to IEC 60947-2 Icu at 500 V DC 2P conforming to IEC 60947-2 Icu at 48/125 V DC 1P conforming to IEC 60947-2 Icu at 250 V DC 1P conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| Device Full Name | Schneider Electric LV438019 |